(3) Using the scaling function (for example in the Q68AD-G) to change a resolution
If the module after replacement (for example, the Q68AD-G) supports the scaling function
can be changed using this function.
(Condition)
(a) Resolution of an A series analog I/O module: 1/8000 (Only one channel is used.)
(b) Q series analog I/O module: Q68AD-G
(Example of sequence program to set the function and read the scaling value)
Setting request
condition
Present value
read condition
(Buffer memory areas of the Q68AD-G)
Address
Hexadecimal
35
H
36
H
37
H
38
H
39
H
3A
H
3B
H
3C
H
3D
H
3E
H
3F
H
40
H
41
H
*1
For details of the scaling function, refer to the user's manual for the module used.
App
- 7
TOP
H0
K53
TOP
H0
K62
TOP
H0
K63
FROMP H0
K34
Description
Decimal
53
Scaling enable/disable setting
54
CH1 Scaling value
55
CH2 Scaling value
56
CH3 Scaling value
57
CH4 Scaling value
58
CH5 Scaling value
59
CH6 Scaling value
60
CH7 Scaling value
61
CH8 Scaling value
62
CH1 Scaling lower limit value
63
CH1 Scaling upper limit value
64
CH2 Scaling lower limit value
65
CH2 Scaling upper limit value
Enable the scaling function of
K1
K1
Channel 1.
Set the scaling lower limit
K0
K1
value to "0".
Set the scaling upper limit
K8000
K1
value to "8000".
Read the scaling value of
D0
K1
Channel 1 from the buffer memory.
*1
, a resolution
Default
Read/Write
00FF
R/W
H
0
0
0
0
R
0
0
0
0
0
0
R/W
0
0