Buffer Memory Address Comparison - Mitsubishi Electric MELSEC-A/QnA Series Handbook

Table of Contents

Advertisement

2
ANALOG INPUT MODULE REPLACEMENT

2.6.4 Buffer memory address comparison

Sequence program change is required as the assignment of buffer memory differs.
For details of the I/O signals or sequence program, refer to the Channel Isolated Analog-Digital
Converter Module, Channel Isolated Analog-Digital Converter Module (With Signal Conditioning
Function) User's Manual.
A68AD-S2
Address
Name
(Dec.)
0
Used channel specification
1
Averaging processing specification
2
CH1 Averaging time, count
3
CH2 Averaging time, count
4
CH3 Averaging time, count
5
CH4 Averaging time, count
6
CH5 Averaging time, count
7
CH6 Averaging time, count
8
CH7 Averaging time, count
9
CH8 Averaging time, count
10
CH1 Digital output value
11
CH2 Digital output value
12
CH3 Digital output value
13
CH4 Digital output value
14
CH5 Digital output value
15
CH6 Digital output value
16
CH7 Digital output value
17
CH8 Digital output value
18
19
20
21
22
23
24
25
System area (Not used)
26
27
28
29
30
31
32
33
34
Write data error code
35
A/D conversion completed flag
2
- 41
Address
Read/write
(Dec.)
0
A/D conversion enable/disable
CH1 Average time/Average number of times/
1
Moving average/Time constant settings
CH2 Average time/Average number of times/
2
Moving average/Time constant settings
CH3 Average time/Average number of times/
3
Moving average/Time constant settings
CH4 Average time/Average number of times/
4
Moving average/Time constant settings
R/W
CH5 Average time/Average number of times/
5
Moving average/Time constant settings
CH6 Average time/Average number of times/
6
Moving average/Time constant settings
CH7 Average time/Average number of times/
7
Moving average/Time constant settings
CH8 Average time/Average number of times/
8
Moving average/Time constant settings
9
System area (Not used)
10
A/D conversion completed flag
11
CH1 Digital output value
12
CH2 Digital output value
13
CH3 Digital output value
R
14
CH4 Digital output value
15
CH5 Digital output value
16
CH6 Digital output value
17
CH7 Digital output value
18
CH8 Digital output value
19
Error code
20
Setting range (CH1 to CH4)
21
Setting range (CH5 to CH8)
22
Offset/gain setting mode Offset specification
23
Offset/gain setting mode Gain specification
Averaging process specification (CH1 to
24
CH4)
Averaging process specification (CH5 to
25
-
CH8)
26
27
System area (Not used)
28
29
30
CH1 Maximum value
31
CH1 Minimum value
32
CH2 Maximum value
33
CH2 Minimum value
R/W
34
CH3 Maximum value
R
to
44
CH8 Maximum value
45
CH8 Minimum value
Q68AD-G
Name
Read/write
R/W
R/W
-
R
-
R

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Melsec q series

Table of Contents