TEMPERATURE INPUT MODULE REPLACEMENT
16-bit signed binary (Scaling value)
(-2700 to 18200: value up to the first decimal place × 10)
Refer to Section 4.2.1 (2).
Refer to Section 4.2.1 (2).
Isolation
Isolated area
method
Between
Transformer
thermocouple
isolation
input and earth
Between
Transformer
thermocouple
isolation
input channels
Between cold junction
compensation
Non-isolation
input (Pt100)
and ground
(I/O assignment: intelligent 16 points)
18-point terminal block
(Sleeved solderless terminal cannot be used.)
Q64TD
-270 to 1820°C
16-bit signed binary
*1
40ms/channel
Dielectric withstand
Insulation
voltage
resistance
500VDC 100M
or more
1780VrmsAC/3 cycles
(altitude 2000m)
500VDC 10M
or more
-
4 channels/module
16 points
2
0.3 to 0.75mm
1.25-3, R1.25-3
0.50A
0.25kg
: Compatible,
Compatibility
-
×
×
×
×
: Partial change required, ×: Incompatible
Precautions for replacement
As the applicable thermocouples and
thermocouple compliance standards
differ, refer to Section 4.2.1 (2) to
check the specifications, and use the
thermocouple that can be used with
the Q64TD.
As they depend on the applicable
thermocouple and measured
temperature range, refer to Section
4.2.1 (2) to check the specifications.
Consider replacement with multiple
Q64TD.
The number of occupied I/O points
has changed to 16 points.
Wiring change is required.
4
- 4