Operating Mode 6 (Extlc Via Bms) - Siemens LMV51 Series Basic Documentation

Burner control with integrated fuel / air ratio control and load control for forced-draft burners
Hide thumbs Also See for LMV51 Series:
Table of Contents

Advertisement

Operating mode 6
(extLC via BMS)
60/157
Siemens Building Technologies
HVAC Products
BMS as control with digital predefined load via CAN bus.
The LMV51... system is connected to a BMS via the AZL51... and an external e-bus
interface.
The BMS contains the controller and transmits the load (manipulated variable) and the
heat demand signal to the LMV51... system.
In this operating mode, the load controller inside the LMV51... is not required.
-Predefined output
-Demand for heat
e-bus
BMS
e-bus
interface
Basic Documentation LMV51...
5 Temperature or pressure controller (internal load controller LC)
Internal
load controller
AZL
Manipulated variable,
demand for heat
Manipulated variable,
demand for heat
CAN module
(basic unit)
Manipulated
Demand
variable
for heat
0...100 %
FARC (BU)
BC (BU)
CAN bus
CC1P7550en
29.05.2002