Siemens LMV51 Series Basic Documentation page 151

Burner control with integrated fuel / air ratio control and load control for forced-draft burners
Hide thumbs Also See for LMV51 Series:
Table of Contents

Advertisement

44
#
BU
Controller connected but
1
BU
deactivated
2
BU
APS connected but deactivated
FCC / FGR - APS connected but
3
BU
deactivated
Gas Pressure m in connected but
4
BU
deactivated
Gas Pressure m ax connected but
5
BU
deactivated
Oil Pressure m in connected but
6
BU
deactivated
Oil Pressure m ax connected but
7
BU
deactivated
Start Signal Oil connected but
8
BU
deactivated
HO Start connected but
9
BU
deactivated
45
-
BU
Locked by SLT
50
#
BU
Internal Fault Basic Unit
51
-
BU
Internal Fault Basic Unit
52
#
BU
Internal Fault Basic Unit
58
-
BU
Param eter Set dam aged
59
#
BU
Param eter Set dam aged
5A
#
BU
Param eter Set dam aged
5B
#
BU
Param eter Set dam aged
5C
#
BU
Param eter Backup Restore
5D
#
BU
Internal Fault Basic Unit
Siemens Building Technologies
Basic Documentation LMV51...
HVAC Products
13 Addendum 1: List of error messages of LMV51... system
Fault with inputs deactivated
Controller input connected but deactivated
APS connected but deactivated
FCC / FGR-APS connected but deactivated
GP m in connected but deactivated
GP m ax connected but deactivated
OP m in connected but deactivated
OP m ax connected but deactivated
Start signal oil connected but deactivated
HO start connected but deactivated
Shutdown after SLT test
Key error
Tim e block overrun
Stack fault
Internal com m unication (µC1 <> µC2)
EEPROM page on ABORT after initialization (last
param eter setting has possibly been interrupted
by a power failure)
Param eter page with CRC fault
Page is on ABORT
Page is on W R_RESTO
Page open for too long
*1)
*1)
*1)
*1)
Reset the unit.
!Caution! If this fault occurred while setting the param eters: Check the
param eters changed last to ensure they are correct
If resetting does not solve the problem : Restore the param eters of the AZL51...
Otherwise, replace the basic unit
Reset the unit
!Caution! If this fault occurred while setting the param eters: Check the
param eters changed last to ensure they are correct
If resetting does not solve the problem : Restore the param eters of the AZL51...
Otherwise, replace the basic unit
Reset the unit
Reset the unit
!Caution! If this fault occurred while setting the param eters: Check the
param eters changed last to ensure they are correct
If resetting does not solve the problem : Restore the param eters of the AZL51...
Otherwise, replace the basic unit
151/157
CC1P7550en
29.05.2002