Siemens LMV51 Series Basic Documentation page 122

Burner control with integrated fuel / air ratio control and load control for forced-draft burners
Hide thumbs Also See for LMV51 Series:
Table of Contents

Advertisement

Menu level 1
Menu level 2
Params & Display
RatioControl
Changing an existing
curve
Menu level 1
Menu level 2
Params & Display
RatioControl
122/157
Siemens Building Technologies
HVAC Products
During storage, the LMV51... sorts the curvepoints based on rising output. This means
that you can enter the curvepoints in any order you like as long as the output was
correctly set.
Proceed in this way point by point until the minimum output is reached. After storage of
the minimum output point, leave the curve setting.
Menu level 3
GasSettings
Example:
Point
Order of setting
Output
15 %
Gas
Air
10.5°
Aux
20.3°
Fuel / air ratio control
90
80
70
60
50
40
30
20
10
0
0
10
20
The curvepoints can be changed during burner off periods (Phase 12) or during burner
operation (Phase 60).
To change an existing curve, select the curvepoint in «Point» mode. You are now able
to change the point, or to cancel it.
Menu level 3
GasSettings
Basic Documentation LMV51...
7 Commissioning instructions for the LMV51... system
Menu level 4
Menu level 5
CurveParams
Point
Manual
1
2
5
4
28 %
8.6°
28.0°
28.8°
30.0°
30
40
50
Load [%]
Menu level 4
CurveParams
Menu level 6
3
4
3
2
50 %
71 %
43.0°
62.5°
46.0°
55.7°
45.0°
52.0°
Gas actuator position
Air actuator position
Auxiliary actuator
60
70
80
Menu level 5
Menu level 6
Point
Manual
5
1
100 %
81.5°
70.8°
60.0°
90
100 %
CC1P7550en
29.05.2002