7. Setting the load
controller (option)
Menu level 1
Menu level 2
Params & Display
LoadController
8. Selecting a temperature
or pressure sensor
Menu level 1
Menu level 2
Params & Display
LoadController
Siemens Building Technologies
HVAC Products
Menu level 3
Configuration
Select a load controller operating mode in accordance with the examples given in
chapter «Operating modes with load controller».
If the internal load controller of the LMV51... is used, a temperature or pressure sensor
must be connected to input 1, 2 or 4.
Menu level 3
Configuration
On the configuration level of the LC, select the required type of sensor.
Then, define the sensor's measuring range.
Basic Documentation LMV51...
7 Commissioning instructions for the LMV51... system
Menu level 4
Menu level 5
LC_OptgMode
Menu level 4
Menu level 5
Inp1/2/4Sel
Inp1/4/MaxValue
Inp2Config_C/V
Inp2TempMaxValue
Inp2PresMaxValue
Inp3Config_C/V
Inp3MinSetpoint
Inp3MaxSetpoint
Menu level 6
Menu level 6
119/157
CC1P7550en
29.05.2002