4.5.1 Set Fire Source Shielded Region

Steps
1. Go to Configuration → Local , and enable Display Shield Area.
2. Go to Configuration → Event → Smart Event → Fire Source Region Shield .
3. Check Enable Fire Source Detection Shield .
4. Select Drawing Mode, and draw the area you want to shield.
In
Select this mode if the shielded area is in the current scene.
FOV
a. Click the PTZ control buttons to find the area you want to shield from the fire
detection.
b. Click Draw Area, and drag the mouse in the live view to draw the area.
c. You can drag the corners of the red rectangle area to change its shape and size.
d. Click Stop Drawing to finish drawing, or click Clear All to clear all of the areas you
set without saving them.
Out
Select this mode if the shielded area exceeds the current scene.
FOV
a. Click Draw Area, and a red cursor displays in live view.
b. Select Vertex NO. 1, and adjust the live view image by clicking the PTZ control
buttons.
c. When one corner of the shielded area is on the red cursor, click Set Vertex.
d. Repeat steps b-c to set other three vertexes.
e. Click Stop Drawing to finish drawing, or click Clear All to clear all of the vertexes
you set.
Note
• Set vertexes clockwise or anticlockwise in sequence.
• The pan angle of set area should be from 2 to 80 degrees, and tilt angle should be from 1 to
45 degrees.
• Draw four vertexes again if you want to change the shielded area.
5. Check Display Shield Area to show the shield area on the live view.
6. Click Add to save the fire detection shield, and it will be listed in the Fire Source Detection
Shield List area; you can select a region and click Delete to delete it from the list; you can also
define the color of the regions.
7. Click Save.

4.6 Set Smoke Detection Parameters

To avoid the potential smoke damage, you should configure the smoke detection function for
certain areas. The detail configuration steps show as below.
Steps
1. Go to Configuration → Event → Smart Event , select Fire and Smoke Detection.