10.9.4
Suction Temperature Sensor Fault
This alarm is generated to indicate that the sensor is not reading properly.
Symptom
Circuit status is Off.
The circuit is switched off with the
normal shutdown procedure.
Bell icon is moving on controller's
display.
String in the alarm list:
CxCmp1 OffSuctTempSen
String in the alarm log:
CxCmp1 OffSuctTempSen
String in the alarm snapshot
CxCmp1 OffSuctTempSen
Reset
Local HMI
Network
Auto
10.9.5
Discharge Temperature Sensor Fault
This alarm is generated to indicate that the sensor is not reading properly.
Symptom
Circuit status is Off.
The circuit is switched off with the
normal shutdown procedure.
Bell icon is moving on controller's
display. String in the alarm list:
CxCmp1 OffDischTmpSen
String in the alarm log:
CxCmp1 OffDischTmpSen
String in the alarm snapshot
CxCmp1 OffDischTmpSen
Reset
Local HMI
Network
Auto
59/77
Cause
Sensor is shorted.
Sensor is broken.
Sensor is not good connected (open).



Cause
Sensor is shorted.
Sensor is broken.
Sensor is not properly connected
(open).



Operation Manual
Solution
Check for sensor integrity.
Check correct sensors operation
according information about kOhm
(k ) range related to temperature
values.
Check if sensor is shorted with a
resistance measurement.
Check for correct installation of the
sensor on refrigerant circuit pipe.
Check for absence of water or
humidity on sensor electrical
contacts.
Check for correct plug-in of the
electrical connectors.
Check for correct sensors wiring also
according with electrical scheme.
Notes
Solution
Check for sensor integrity.
Check correct sensors operation
according information about kOhm
(k ) range related to temperature
values.
Check if sensor is shorted with a
resistance measurement.
Check for correct installation of the
sensor on refrigerant circuit pipe.
Check for absence of water or
humidity on sensor electrical
contacts.
Check for correct plug-in of the
electrical connectors.
Check for correct sensors wiring also
according with electrical scheme.
Notes
D–EOMWC00A07-16_02EN