Daikin MICROTECH III Operating Manual page 48

Water-cooled screw chiller
Hide thumbs Also See for MICROTECH III:
Table of Contents

Advertisement

10.8.2
Low Pressure Start Fail
This alarm indicates that at the compressor start the evaporating pressure or condensing pressure is below a minimum
fixed limit at compressor start.
Symptom
Circuit status is Off.
The circuit is stopped.
Bell icon is moving on controller's
display.
String in the alarm list:
Cx OffStartFailEvpPrLo
String in the alarm log:
Cx OffStartFailEvpPrLo
String in the alarm snapshot
Cx OffStartFailEvpPrLo
Reset
Local HMI
Network
Auto
D–EOMWC00A07-16_02EN
Cause
Ambient temperature is too low
(Condenserless units) or evaporator
water temperature is too low (W/C
units)
Circuit refrigerant charge is too low



Operation Manual
Solution
Check the operating envelope for this
machine.
Check refrigerant charge.
Check for gas leakage with a sniffer.
Notes
48/77