6-13.Monitoring Detailed Operation Status - Daikin DCS004A51 Operation Manual

Intelligent touch controller web software
Table of Contents

Advertisement

3. Click the "
ton to display the Abnormal history screen (Screen 3). In this
screen you can check errors that the selected devices have
encountered. If no error has occurred, the Screen 4 appears.
Screen 3:
Abnormal history screen
Click the "
" button to return to the Information
screen.
Error event information including the time occurred, error code,
and error unit number are recorded and sorted by time
occurred. Up to 10 historical error events can be recorded.
When an error event with the same error code as one for the
already registered event occurs in a specific group, only the time
is updated. For a specific group two or more error events with
the same error code are not registered.
6-13 Monitoring Detailed Operation Status
I I I I Procedure for monitoring detailed operation status
Detailed operation status can be monitored by zone or by group.
Screen 1: Main screen
(1)
[Procedure]
1. To view information on a zone, select the "Monitoring (Zone
list)" item from the zone tree area (1). To view information on
a group, select the zone including the group from the zone
tree area. Then select the target zone or group in the main
display area (2).
32
" ((3) on the previous page) but-
Screen 4:
Abnormal history screen
(2)
2. Click the "
(Screen 2).
This screen provides the following information.
Screen 2: Setup screen
(1)
(2)
(3)
(5)
(6)
(7)
(1) Name (Description)
Displays the name and description of a zone or group.
(2) Current Condition
• Start/Stop state
• Operation Mode
(3) Air volume
Displays current air volume.
(4) Direction of air flow
Displays current direction of air flow.
The area under the R/C Mode heading includes three frames to
display the setting for permission/prohibition of operation
through remote controller. In each frame one of the following
options are highlighted.
(5) Start/Stop
"Permitted"
"Stop Only"
"Prohibited"
(6) Operation Mode
"Permitted" or "Prohibited"
(7) Set Temperature
"Permitted" or "Prohibited"
3. Upon completion, click the "
to the Main screen.
CAUTION
This screen can be used for both setting and monitoring.
When using it only for monitoring, be sure to click the
"
" button, rather than the "
This prevents you from inadvertently changing existing
settings.
" button to display the Setup screen
(4)
• Room temperature
• Presence or absence of filter
signs
" (8) button to return
" to close it.
(8)
English