600 HD INSTALLATION INSTRUCTIONS
Installation with a flexible liner
The 600 HD is designed for installation within the masonry chimney with or without a flexible line.
If the flexible liner option is required the following two methods should be followed.
Method 1
A 125mm minimum diameter liner conforming to BS 715 may be used. Providing a suitable
sealing plate is fitted to the base of the liner and the appliance does not restrict the opening
into the liner. Ensure a smooth lead into the flue way and no combustible materials are used. A
void of 50mm must be maintained from the top of the firebox into flue.
Method 2
Using the flexible liner gather hood (Part No A-0662). Using again 125mm minimum diameter liner
conforming to BS 715, route the flexible liner within the masonry as of the requirements stipulated
by the liner manufacturer.
Attach the gather hood to the liner using a suitable fixing at a height that clears the firebox
assembly.
Remove the inner and outer inspection plate situated within the rear of the fire box assembly
(Please see Fig 1).
LT7618 Issue No 1 (06/2018)
P a g e
| 27