Danfoss VLT Refrigeration Drive FC 103 Operating Instructions Manual page 56

1.1-90 kw
Hide thumbs Also See for VLT Refrigeration Drive FC 103:
Table of Contents

Advertisement

Specifications
380-480 V
Enclosure
type
A2
A3
B3
B4
C3
C4
A4
A5
B1
B2
8
8
C1
C2
Table 8.9 380-480 V, Enclosure Types A, B and C
525-600 V
Enclosure
type
A3
B3
B4
C3
C4
A5
B1
B2
C1
C2
Table 8.10 525-600 V, Enclosure Types A, B and C
54
Power [kW]
Recommended
fuse size
1.1-4.0
gG-10 (1.1-3)
gG-16 (4)
5.5-7.5
gG-16
11-18
gG-40
22-37
gG-50 (22)
gG-63 (30)
gG-80 (37)
45-55
gG-100 (45)
gG-160 (55)
75-90
aR-200 (75)
aR-250 (90)
1.1-4
gG-10 (1.1-3)
gG-16 (4)
1.1-7.5
gG-10 (1.1-3)
gG-16 (4-7.5)
11-18.5
gG-40
22-30
gG-50 (22)
gG-63 (30)
37-55
gG-80 (37)
gG-100 (45)
gG-160 (55)
75-90
aR-200 (75)
aR-250 (90)
Power [kW]
Recommended
fuse size
5.5-7.5
gG-10 (5.5)
gG-16 (7.5)
11-18
gG-25 (11)
gG-32 (15-18)
22-37
gG-40 (22)
gG-50 (30)
gG-63 (37)
45-55
gG-63 (45)
gG-100 (55)
75-90
aR-160 (75)
aR-200 (90)
1.1-7.5
gG-10 (1.1-5.5)
gG-16 (7.5)
11-18
gG-25 (11)
gG-32 (15)
gG-40 (18.5)
22-30
gG-50 (22)
gG-63 (30)
37-55
gG-63 (37)
gG-100 (45)
aR-160 (55)
75-90
aR-200 (75-90)
Danfoss A/S © Rev. 2014-02-06 All rights reserved.
Operating Instructions
Recommended
max. fuse size
gG-25
gG-32
gG-63
gG-125
gG-150 (45)
gG-160 (55)
aR-250
gG-32
gG-32
gG-80
gG-100
gG-160
aR-250
Recommended
max. fuse size
gG-32
gG-63
gG-125
gG-150
aR-250
gG-32
gG-80
gG-100
gG-160 (37-45)
aR-250 (55)
aR-250
Recommended circuit
Max. trip level [A]
breaker (Moeller)
PKZM0-25
PKZM0-25
PKZM4-50
NZMB1-A100
NZMB2-A200
NZMB2-A250
PKZM0-25
PKZM0-25
PKZM4-63
NZMB1-A100
NZMB2-A200
NZMB2-A250
Recommended circuit
Max. trip level [A]
breaker (Moeller)
PKZM0-25
PKZM4-50
NZMB1-A100
NZMB2-A200
NZMB2-A250
PKZM0-25
PKZM4-63
NZMB1-A100
NZMB2-A200
NZMB2-A250
25
25
50
100
150
250
25
25
63
100
160
250
25
50
100
150
250
25
63
100
160
250
MG16E302