11. Attach and tighten both transmitter covers.
2.2
Typical European installation
Figure 2-2: Typical Remote-Mounted Configuration with Cable Glands
A. Cable gland
B. Shielded cable from sensor to transmitter
C. Shielded cable from transmitter to control room
D. 2-in. (50 mm) pipe
E. B4 mounting bracket
Procedure
1. Mount the thermowell to the process container wall.
2. Install and tighten thermowells.
3. Perform a leak check.
4. Attach a connection head to the thermowell.
5. Insert sensor into the thermowell and wire the sensor to the
connection head.
The wiring diagram is located inside the connection head.
6. Mount the transmitter to a 2-in. (50 mm) pipe or a panel using one of
the optional mounting brackets.
7. Attach cable glands to the shielded cable running from the
connection head to the transmitter conduit entry.
8. Run the shielded cable from the opposite conduit entry on the
transmitter back to the control room.
9. Insert shielded cable leads through the cable entries into the
connection head/transmitter. Connect and tighten cable glands.
10. Connect the shielded cable leads to the connection head terminals
(located inside the connection head) and to the sensor wiring
terminals (located inside the transmitter housing).
6
A
B
C
March 2020
D
E
Rosemount 3144P