The following is the minimum configuration requirement for a temperature
measurement. This guide is designed for systems not using DD methods. For
a complete list of parameters and configuration information, refer to the
Rosemount 3144P Temperature Transmitter
4.2
Transducer function block
This block contains temperature measurement data for the sensors and the
terminal temperature. It also includes information about sensor types,
engineering units, damping, and diagnostics.
At a minimum, verify the parameters in
Table 4-1: Transducer Block Parameters
Parameter
Typical configuration
SENSOR_TYPE_X
SENSOR_CONNECTIONS_X
Sensor matching configuration
SENSOR_TYPE_X
SENSOR_CONNECTIONS_X
SENSOR_CAL_METHOD_X
SPECIAL SENSOR_A_X
SPECIAL SENSOR_B_X
SPECIAL SENSOR_C_X
SPECIAL_SENSOR_R0_X
4.2.1
Analog Input (AI) function block
The AI block processes field device measurements and makes the outputs
available to other function blocks. The output value of the AI block is in
engineering units and contains a status indicating the quality of the
measurements. Use the channel number to define the variable that the AI
block processes.
At a minimum, verify the parameters of each AI block in
Note
All devices ship with the AI blocks scheduled, meaning the operator does not
need to configure the block or he or she uses factory default channels.
Table 4-2: AI Block Parameters
Configure one AI Block for each desired measurement.
Quick Start Guide
Reference
Manual.
Table
4-1.
Comments
Example: "Pt 100_A_385 (IEC 751)"
Example: "2-wire", "3-wire", "4-wire"
"User Defined, Calvandu"
Example: "2-wire", "3-wire", "4-wire"
Set to "User Trim Standard"
Enter sensor specific coefficients
Enter sensor specific coefficients
Enter sensor specific coefficients
Enter sensor specific coefficients
Table
Quick Start Guide
4-2.
13