Emerson Rosemount 3144P Quick Start Manual page 14

Temperature transmitters with foundation fieldbus protocol
Hide thumbs Also See for Rosemount 3144P:

Advertisement

Quick Start Guide
Parameter
CHANNEL
LIN_TYPE
XD_SCALE
OUT_SCALE
HI_HI_LIM
HI_LIM
LO_LIM
LO_LO_LIM
14
Comments
Choices:
1. Sensor 1 Temperature
2. Sensor 2 Temperature
3. Differential Temperature
4. Terminal Temperature
5. Sensor 1 Min. Value
6. Sensor 1 Max. Value
7. Sensor 2 Min. Value
8. Sensor 2 Max. Value
9. Differential Min. Value
10. Differential Max. Value
11. Terminal Temp Min. Value
12. Terminal Temp Max. Value
13. Hot Backup
This parameter defines the relationship between the block
input and the block output. Since the transmitter does not
require linearization, this parameter will always be set to No
Linearization. This means that the AI block will only apply
scaling, filtering, and limit checking to the input value.
Set desired measurement range and units. Units must be one
of the following:
mV
Ohms
°C
°F
°R
K
For "DIRECT" L_TYPE, set OUT_SCALE to match XD_SCALE
Process alarms.
Must be within the range defined by "OUT_SCALE"
March 2020
Rosemount 3144P