Emerson Rosemount 3144P Quick Start Manual page 19

Temperature transmitters with foundation fieldbus protocol
Hide thumbs Also See for Rosemount 3144P:

Advertisement

March 2020
5.4.3
N1 ATEX Type n
Certificate BAS01ATEX3432X [HART]; Baseefa03ATEX0709X [Fieldbus]
Standards EN IEC 60079-0:2018, EN 60079-15:2010
Markings
Special Condition for Safe Use (X):
1. When fitted with the transient terminal options, the equipment is
not capable of passing the 500 V electrical strength test as defined in
clause 6.5.1 of EN 60079-15: 2010. This must be taken into account
during installation.
5.4.4
ND ATEX Dust
Certificate FM12ATEX0065X
Standards EN 60079-0: 2012+A11:2013, EN 60079-31:2014, EN
Markings
Specific Conditions of Use (X):
1. See certificate for ambient temperature range.
2. The non-metallic label may store an electrostatic charge and become
a source of ignition in Group III environments.
3. Guard the LCD display cover against impact energies greater than
four joules.
4. Flameproof joints are not intended for repair.
5. A suitable certified Ex d or Ex tb enclosure is required to be connected
to temperature probes with Enclosure option "N".
6. Care shall be taken by the end user to ensure that the external
surface temperature on the equipment and the neck of DIN Style
Sensor probe does not exceed 266 °F (130 °C).
7. Non-standard paint options may cause risk of electrostatic discharge.
Avoid installations that cause electrostatic build-up on painted
surfaces and only clean the painted surfaces with a damp cloth. If
paint is ordered through a special option code, contact the
manufacturer for more information.
Quick Start Guide
HART:
II 3 G Ex nA IIC T5/T6 Gc; T6(-40 °C ≤ T
T5(-40 °C ≤ T
≤ +75 °C);
a
Fieldbus:
II 3 G Ex nA IIC T5 Gc; T5(-40 °C ≤ T
60529:1991 +A1:2000+A2:2013
II 2 D Ex tb IIIC T130°C Db, (-40 °C ≤ T
See
Process temperature limits
Quick Start Guide
a
≤ +75 °C);
a
≤ +70 °C); IP66
a
for process temperature.
≤ +50 °C),
19