Emerson Rosemount 3144P Quick Start Manual page 15

Temperature transmitters with foundation fieldbus protocol
Hide thumbs Also See for Rosemount 3144P:

Advertisement

March 2020
Note
To make changes to the AI block, set the BLOCK_MODE (TARGET) to OOS
(out of service). After making the changes, return the BLOCK_MODE
TARGET to AUTO.
4.2.2
Set switches
The security and simulate switches are located on the top center of the
electronics module.
Note
The factory ships the simulate switch in the "ON" position.
Set the switches with an LCD display
Procedure
1. Set the loop to manual (if applicable) and disconnect the power.
2. Remove the electronics housing cover.
3. Unscrew the LCD display screws and gently slide the meter straight
off.
4. Set the alarm and security switches to the desired position.
5. Gently slide the LCD display back into place.
6. Replace and tighten the LCD display screws to secure the LCD
display.
7. Reattach housing cover.
8. Apply power and set the loop to automatic control.
Set the switches without an LCD display
Procedure
1. Set the loop to manual (if applicable) and disconnect the power.
2. Remove the electronics housing cover.
3. Set the alarm and security switches to the desired position.
4. Reattach housing cover.
5. Apply power and set the loop to automatic control.
Quick Start Guide
Quick Start Guide
15