InfiNET
Lamp Dimmer
CLF-DIMRFB Troubleshooting (Continued)
TROUBLE
Dimmer
does not
respond to
control
system
commands.
(Continued on following page)
20 • infiNET
™
Lamp Dimmer: CLF-DIMRFB
POSSIBLE
CAUSE(S)
If the LED blinks OFF
for ¼ second four
times, then returns to
LOW every eight
seconds, the dimmer
is not currently
communicating with a
C2N-MNETGW.
If the LED blinks OFF
for ¼ second two
times, then returns to
LOW every eight
seconds, the MNET
ID of device (or the
gateway ID) is not set
to match the MNET
ID of the SIMPL
Windows program.
Crestron CLF-DIMRFB
CORRECTIVE
ACTION
Open Crestron
Toolbox and select
the Network Device
Tree. Expand the tree
until the gateway to
be managed is
selected.
Right-click the NET ID
of the selected
gateway to open the
sub-menu and select
Functions|MNET
Gateway... If devices
are not listed, acquire
the device to the
infiNET network as
described in "Enter
ACQUIRE Mode" on
page 16.
Use the Network
Device Tree infiNET
network in Crestron
Toolbox to poll the
infiNET network.
Verify that the MNET
ID for the infiNET
device is set to match
the MNET ID
specified in the SIMPL
Windows program.
Operations Guide – DOC. 6479