1.2 I Hydraulic connections

1.2.1 Pool water circuit
• The connection is made with a Ø50 PVC pipe to the pool filtration circuit, after the filter and before the water
treatment, using the unions supplied.
• Ensure that the hydraulic connection fitting direction is correct.
• A by-pass must be installed to make it easier to work on the appliance.
• Use the valve
to adjust the water flow and leave the valves
1.2.2 Dehumidifier water circuit
• Provide a connection between the heat pump and the dehumidifier.
• The connection is made with Ø28 insulated pipes, using the union connectors supplied (12 metres maximum. Contact
our design office for any additional information). The piping must be compatible with the maximum temperature of
the appliance (please see § "5.2 I Technical specifications").
• Do not use quick closure valves to avoid water hammer.
• Check that the pipe system is cleaned before making any connection.
: Pool water inlet valve
: Pool water by-pass valve
: Pool water outlet valve
: Pool water inlet adjusting valve(optional)
: Pool water outlet adjusting valve(facultative)
,
,
and
: Dehumidifier water inlet valve (optional)
: Dehumidifier water outlet valve (optional)
: Dehumidifier water hydraulic connection kit
: Mains cold water inlet
* Minimum distance
** Maximum distance
open (refer to diagram below)