Power Supply Connection - ControlByWeb WebRelay-Quad X-WR-4R1-5 User Manual

Hide thumbs Also See for WebRelay-Quad X-WR-4R1-5:
Table of Contents

Advertisement

Revision 2.2b
14-pin connector pinout:
Pin
Description
VIN+
Power supply input. Connect to the positive side of the appropriate power supply. DO NOT
EXCEED MAXIMUM POWER SUPPLY VOLTAGE.
Model X-WR-4R1-5
5VDC Power supply
Model X-WR-4R1-I
9~28VDC Power supply
Model X-WR-4R1-E
Power Over Ethernet model. These units do not require a power supply to be connected to this
pin when the unit is connected to an 802.3af compliant network. Alternatively, this model can be
powered using a 5VDC power supply.
VIN-
Power supply ground (-) connection.
1C
Relay 1 Common Contact
1NC
Relay 1 Normally Closed Contact
1NO
Relay 1 Normally Open Contact
2C
Relay 2 Common Contact
2NC
Relay 2 Normally Closed Contact
2NO
Relay 2 Normally Open Contact
3C
Relay 3 Common Contact
3NC
Relay 3 Normally Closed Contact
3NO
Relay 3 Normally Open Contact
4C
Relay 4 Common Contact
4NC
Relay 4 Normally Closed Contact
4NO
Relay 4 Normally Open Contact

2.2.1 Power Supply Connection

WebRelay-Quad
TM
Vin+ and Vin- terminals. Alternatively, WebRelay-Quad
be powered through the Ethernet connection instead of using an external power supply.
Multiple WebRelay-Quad
supply input terminals in parallel. The power supply must have a high enough current rating to power all
units connected (see specifications for current requirements for a specific model number).
WebRelay-Quad
TM
Ethernet port instead of connecting an external power supply. In this case, WebRelay-Quad
through the network port. In an 802.3af compliant network, a 48 Volt power source is injected into the
Ethernet line. This power source is provided by an 802.3af compliant hub, switch, or power injector which
may be located in a utility closet which could be a distance away from WebRelay-Quad
very useful for installations where local power is not available. The power injector may inject the 48 Volt
power source through the data lines or the spare lines in the Ethernet cable. DO NOT USE A POWER
INJECTOR THAT APPLIES A VOLTAGE TO BOTH THE DATA LINES AND THE SPARE LINES.
Xytronix Research & Design, Inc.
requires power for its internal logic circuits. Connect appropriate power supply to the
units may be connected to a single power supply by connecting the power
TM
units with the Power Over Ethernet option may be connected to an 802.3af compliant
WebRelay-Quad
units with the Power Over Ethernet option may
TM
Users Manual
TM
is powered
TM
. This option is
TM
page 11

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the WebRelay-Quad X-WR-4R1-5 and is the answer not in the manual?

This manual is also suitable for:

Webrelay-quad x-wr-4r1-iWebrelay-quad x-wr-4r1-e

Table of Contents