GE LPS-D Instruction Manual page 359

Line protection system
Table of Contents

Advertisement

APPENDIX B
Table B–4: MODBUS MEMORY MAP: SETPOINTS
Register
DDE Item Name
Address
(Mnemonic)
R44075I
G3_A10
R44076I
G3_A11
R44077I
G3_A12
R44078I
G3_C1
R44079I
G3_C2
R44080I
G3_KT1
R44081I
G3_KT2
R44082I
G3_KT3
R44083I
G3_KT4
R44084I
G3_CONFTRIP
R44085I
G3_CONFOSC
R44100I
G4_Z1PHASE
R44101F
G4_Z1PHREACH
R44103F
G4_Z1PLEVDET
R44105I
G4_Z1GROUND
R44106F
G4_Z1GRDREACH
R44108I
G4_Z1GRDCHAR
R44109F
G4_Z1SUREACH
R44111F
G4_Z1GROUNDK0
R44113F
G4_Z1GLEVDET
R44115I
G4_Z1BLOCK
R44116I
G4_Z2PHASE
R44117F
G4_Z2PHREACH
R44119I
G4_Z2PCHARANG
R44120I
G4_Z2GROUND
R44121I
G4_Z2GRDCHAR
R44122F
G4_Z2GRDREACH
R44124I
G4_Z2GCHARANG
R44125I
G4_Z2TIMERS
R44126F
G4_Z2P_TIME
R44128F
G4_Z2G_TIME
R44130I
G4_Z3PHASE
R44131F
G4_Z3PHREACH
GE Power Management
(Sheet 21 of 27)
Contents
Units/Value/Range
A10
0 to 256 step 1
A11
0 to 256 step 1
A12
0 to 256 step 1
C1
0 to 256 step 1
C2
0 to 256 step 1
KT1
0 to 256 step 1
KT2
0 to 256 step 1
KT3
0 to 256 step 1
KT4
0 to 256 step 1
CONFTRIP
0 to 256 step 1
CONFOSC
0 to 256 step 1
Z1PHASE
0 = No; 1 = Yes
0.01 to 50.0 Ω step 0.01 (5A)
Z1PHREACH
0.05 to 250.0 Ω step 0.05 (1A)
Z1PLEVDET
0.0 to 9.9 p.u. V step 0.1
Z1GROUND
0 = No; 1 = Yes
0.01 to 50.0 Ω step 0.01 (5A)
Z1GRDREACH
0.05 to 250.0 Ω step 0.05 (1A)
Z1GRDCHAR
0 = Mho; 1 = React
0.01 to 50.0 Ω step 0.01 (5A)
Z1SUREACH
0.05 to 250.0 Ω step 0.05 (1A)
Z1GROUNDK0
1.0 to 7.0 step 0.1
ZIGLEVDET
0.0 to 9.9 p.u. V step 0.1
Z1BLOCK
0 = No; 1 = Yes
Z2PHASE
0 = No; 1 = Yes
0.01 to 50.0 Ω step 0.01 (5A)
Z2PHREACH
0.05 to 250.0 Ω step 0.05 (1A)
Z2PCHARANG
90 to 120° step 5
Z2GROUND
0 = No; 1 = Yes
Z2GRDCHAR
0 = MHO; 1 = GDOC;
2 = MHOGDOC
0.01 to 50.0 Ω step 0.1 (5A)
Z2GRDREACH
0.05 to 250.0 Ω step 0.05 (1A)
Z2GCHARANG
90 to 120° step 5
Z2TIMERS
0 = No; 1 = Yes
Z2P_TIME
0.10 to 3.0 sec. step 0.01
Z2G_TIME
0.10 to 3.0 sec. step 0.01
Z3PHASE
0 = No; 1 = Yes
0.01 to 50.0 Ω step 0.1 (5A)
Z3PHREACH
0.05 to 250.0 Ω step 0.05 (1A)
LPS-D Line Protection System
B.1 MEMORY MAPPING
R/W
Format
Code
R/W
INT
R/W
INT
R/W
INT
R/W
INT
R/W
INT
R/W
INT
R/W
INT
R/W
INT
R/W
INT
R/W
INT
R/W
INT
R/W
INT
R/W
Float
R/W
Float
R/W
INT
R/W
Float
R/W
INT
R/W
Float
R/W
Float
R/W
Float
R/W
INT
R/W
INT
R/W
Float
R/W
INT
R/W
INT
R/W
INT
R/W
Float
R/W
INT
R/W
INT
R/W
Float
R/W
Float
R/W
INT
R/W
Float
B-