9 SERVICING
A non-critical failure indicates an interruption potential in the LPS-D protection, but not a total loss. When a
non-critical failure occurs, the LPS-D non-critical alarm contact closes, but the LED remains green. Turn off the
DC input power, then reapply it. The WARN xxx message reappears if the failure still exists.
The non-critical failure message has the format WARN xxx. The xxx field is the numeric code that indicates
the nature of the failure. The WARN message remains on the display until a key is pressed or until the LPS-D
restarts successfully with no self-test failures. See Section 9.2.7 SERVICE SYSTEM STATUS FAILURES for
the list of Warning codes and their meanings.
As an alternative, the Information Status command can be used to display the warning type
directly on the LCD Display.
NOTE
Use Section 9.2.7: SERVICE SYSTEM STATUS FAILURES or the Information Status command to isolate the
cause of the failure. Power down the LPS-D and replace the suspected board, if appropriate. Reapply power; if
the WARN message is gone, then the unit has been successfully repaired. If the message has changed, it is
possible that another board requires replacement.
A system failure indicates a failure of a power system input or that the relay has been disabled by a user com-
mand. It is indicated by the closing of the non-critical alarm contact, by a red LED, or by the closing of the criti-
cal alarm contact. However, no LCD display is provided until the Information Status command is invoked.
Turn off and reapply the dc input power. The non-critical alarm contact is closed if the failure still exists. Use the
Information Status command to determine the cause of the trouble.
a) FAILURE MESSAGES: 960 CPU BOARD
FAIL-FLASH MEMORY
FAIL-STATIC RAM
FAIL-STATIC RAM CRC
FAIL-DPRAM 960 ACCESS
FAIL-I960 INTRPT CONTROLLER
FAIL-CPU TIMER
FAIL-CPU EEPROM
FAIL-CPU CAPRAM
FAIL-CPU RTC
FAIL-CPU WATCHDOG TIMER
FAIL-S/W PROT CONSTANTS
FAIL-S/W CONFG. LOGIC
FAIL-CONFIG S/W VERSION ERROR
FAIL-CPU SYSTEM IN RESET
FAIL-CPU SYSTEM SHUTDOWN
GE Power Management
9.2.5 SERVICING A NON-CRITICAL FAILURE
9.2.7 SERVICE SYSTEM STATUS FAILURES
FAIL-DO FEED BACK
FAIL-LUI LCD DISPLAY
FAIL-IRIGB
FAIL-TRIP CKT #1 CONTINUITY ERROR
FAIL-TRIP CKT #2 CONTINUITY ERROR
FAIL-TRIP CKT #3 CONTINUITY ERROR
FAIL-TRIP CKT #4 CONTINUITY ERROR
FAIL-TRIP CKT #5 CONTINUITY ERROR*
FAIL-TRIP CKT #6 CONTINUITY ERROR*
FAIL-CONFIG H/W MISMATCH
FAIL-NO DMA INTERRUPT
FAIL-RUNTIME SETTINGS AREA
FAIL-EEP CONTENTS ERROR
STAT-DO DISABLED HARDWARE
LPS-D Line Protection System
9.2 TROUBLESHOOTING
9.2.6 LOCATING THE DEFECTIVE BOARD
9
9-
5