12 ASCII COMMUNICATIONS
Table 12–3: ASCII COMMAND LIST (Sheet 2 of 7)
ASCII
Command Description
Command
Mnemonic
VALues
Display the present values
of voltages, currents,
watts, Vars, etc., including
Breaker Health in the
second screen. Press
ENTER to see the second
screen
Display the present values
READings
of voltages, currents,
watts, Vars, etc., and
update them once per
second. The ESC key
stops the update. No
Breaker Health is
displayed.
FAUlts
Display fault reports. The
list of available faults is
displayed first then a
number is chosen to view a
particular fault
GE Power Management
Lowest
Relay Prompt
Level
Password
Needed
Present Values
VA rms: V
VB rms: V
VC rms: V
VA: V degs
VB: V degs
VC: V degs
VIEW
Watts: KW
Pow er Factor
Setting G roup N um ber:1
Breaker 1: Closed
Breaker Health
Phase A accumulated
Amps: 45.2 A
Phase B accumulated
Amps: 11.1 A
Phase C accumulated
Amps: 25.7A
VIEW
FLTNO DATE TIME TRIP
1
07/09/98
15:32:23.6833
Enter Fault Number (press ESC to quit): 1
Report for Fault No: 1
TRIP DATE: 07/03/98
TRIP TIME: 16.32.23.6833
Trip Type(s): Z1
Fault Type: ABG
Relay Operating Time: 488 ms
Breaker Operating Time: 1152 ms
Distance: 9999 miles
ITEM
Prefault Current (A)
Fault Current (A)
Fault Voltage (kV)
Press ENTER to Continue
List of Fault Events:
TIME
16:32:23.7025
16:32:23.7041
Press Y to get oscillography data
Press ESC to quit
Press Any Key to continue
LPS-D Line Protection System
12.1 INTRODUCTION
IA rms: A
IB rms: A
IC rms: A
In rms: A
IA: A degs
IB: A degs
IC: A degs
In: A degs
Vars: kVar
Frequency: Hz
No. of Breakers: 2
Breaker 2: N/A
Breaker Operations:
129
FAULT DISTANCE
TYPE
TYPE
EXT
AG
0.2mi
A
B
C
D
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
EVENT
Oscillography Capture
RMS Oscillography Data
User Response
12
None
Press E for
expanded mode,
ESC to end
Two digit
number, 1 to 16
12-
3