Table B–4: MODBUS MEMORY MAP: SETPOINTS
Register
DDE Item Name
Address
(Mnemonic)
R43805I
G3_Z1GROUND
R43806F
G3_Z1GRDREACH
R43808I
G3_Z1GRDCHAR
R43809F
G3_Z1SUREACH
R43811F
G3_Z1GROUNDK0
R43813F
G3_Z1GLEVDET
R43815I
G3_Z1BLOCK
R43816I
G3_Z2PHASE
R43817F
G3_Z2PHREACH
R43819I
G3_Z2PCHARANG
R43820I
G3_Z2GROUND
R43821I
G3_Z2GRDCHAR
R43822F
G3_Z2GRDREACH
R43824I
G3_Z2GCHARANG
R43825I
G3_Z2TIMERS
R43826F
G3_Z2P_TIME
R43828F
G3_Z2G_TIME
R43830I
G3_Z3PHASE
R43831F
G3_Z3PHREACH
R43833I
G3_Z3PCHARANG
R43834I
G3_Z3GRND
R43835F
G3_Z3GRDREACH
R43837I
G3_Z3GCHARACHAG
R43838F
G3_Z3P_TIME
R43840F
G3_Z3G_TIME
R43842I
G3_Z4PHASE
R43843F
G3_Z4PHREACH
R43845I
G3_Z4PCHRANG
R43846I
G3_Z4GRND
R43847F
G3_Z4GRDREACH
R43849I
G3_Z4GCHARANG
R43850I
G3_Z4DIRECTN
GE Power Management
(Sheet 15 of 27)
Contents
Units/Value/Range
Z1GROUND
0 = No; 1 = Yes
0.01 to 50.0 Ω step 0.01 (5A)
Z1GRDREACH
0.05 to 250.0 Ω step 0.05 (1A)
Z1GRDCHAR
0 = Mho; 1 = React
0.01 to 50.0 Ω step 0.01 (5A)
Z1SUREACH
0.05 to 250.0 Ω step 0.05 (1A)
Z1GROUNDK0
1.0 to 7.0 step 0.1
ZIGLEVDET
0.0 to 9.9 p.u. V step 0.1
Z1BLOCK
0 = No; 1 = Yes
Z2PHASE
0 = No; 1 = Yes
0.01 to 50.0 Ω step 0.01 (5A)
Z2PHREACH
0.05 to 250.0 Ω step 0.05 (1A)
Z2PCHARANG
90 to 120° step 5
Z2GROUND
0 = No; 1 = Yes
Z2GRDCHAR
0 = MHO; 1 = GDOC;
2 = MHOGDOC
0.01 to 50.0 Ω step 0.1 (5A)
Z2GRDREACH
0.05 to 250.0 Ω step 0.05 (1A)
Z2GCHARANG
90 to 120° step 5
Z2TIMERS
0 = No; 1 = Yes
Z2P_TIME
0.10 to 3.0 sec. step 0.01
Z2G_TIME
0.10 to 3.0 sec. step 0.01
Z3PHASE
0 = No; 1 = Yes
0.01 to 50.0 Ω step 0.1 (5A)
Z3PHREACH
0.05 to 250.0 Ω step 0.05 (1A)
Z3PCHARANG
90 to 120° step 5
Z3GRND
0 = No; 1 = Yes
0.01 to 50.0 Ω step 0.1 (5A)
Z3GRDREACH
0.05 to 250.0 Ω step 0.05 (1A)
Z3CHARCHAG
90 to 120° step 5
Z3P_TIME
0.10 to 10.0 sec. step 0.01
Z3G_TIME
0.10 to 10.0 sec. step 0.01
Z4PHASE
0 = No; 1 = Yes
0.01 to 50.0 Ω step 0.01 (5A)
Z4PHREACH
0.05 to 250.0 Ω step 0.05 (1A)
Z4PCHRANG
80 to 120° step 5
Z4GRND
0 = No; 1 = Yes
0.01 to 50.0 Ω step 0.01 (5A)
Z4GRDREACH
0.05 to 250.0 Ω step 0.05 (1A)
Z4GCHARANG
80 to 120° step 5
Z4DIRECTN
0 = Forward; 1 = Reverse
LPS-D Line Protection System
B.1 MEMORY MAPPING
R/W
Format
Code
R/W
INT
R/W
Float
R/W
INT
R/W
Float
R/W
Float
R/W
Float
R/W
INT
R/W
INT
R/W
Float
R/W
INT
R/W
INT
R/W
INT
R/W
Float
R/W
INT
R/W
INT
R/W
Float
R/W
Float
R/W
INT
R/W
Float
R/W
INT
R/W
INT
R/W
Float
R/W
INT
R/W
Float
R/W
Float
R/W
INT
R/W
Float
R/W
INT
R/W
INT
R/W
Float
R/W
INT
R/W
INT
B-