Table B–4: MODBUS MEMORY MAP: SETPOINTS
Register
DDE Item Name
Address
(Mnemonic)
R43899F
G3_PHOVTMDLY
R43901I
G3_V1OVER
R43902F
G3_V1OVINSTPU
R43904F
G3_V1OVTIMPU
R43906F
G3_V1OVTIMDLY
R43908I
G3_V1COMP
R43909F
G3_V1COMRCH
R43911F
G3_VICOMPINPU
R43913F
G3_V1COMPTDPU
R43915F
G3_V1COMPDLY
R43917I
G3_FUSEFAIL
R43918I
G3_ALL_BELOW
R43919I
G3_OUTOFSTEP
R43920I
G3_ALL_3_Z2PH
R43921I
G3_50G_BLOCK
R43922I
G3_Z2TIMETRIP
R43923I
G3_Z3TIMETRIP
R43924I
G3_Z4TIMETRIP
R43925I
G3_Z1PHASTRIP
R43926I
G3_ANYZ2PHASE
R43927I
G3_CONFGTRIP
R43928I
G3_LINEPICKUP
R43929I
G3_BYPASSTL3
R43930F
G3_I1PICKPU
R43932I
G3_REMOTEOPEN
R43933I
G3_TL20PICKUP
R43934I
G3_LINEOVERLD
R43935F
G3_LEVEL1PU
R43937F
G3_LEVEL2PU
R43939F
G3_LEVEL1TDLY
R43941F
G3_LEVEL2TDLY
R43943I
G3_PICKSCHEME
R43944I
G3_NUMRCVR
GE Power Management
(Sheet 17 of 27)
Contents
Units/Value/Range
PHOVTMDLY
0.0 to 10.0 sec. step 0.01
V1OVER
0 = No; 1 = Yes
V1OVINSTPU
1.0 to 1.4 p.u. V step 0.01
V1OVTIMPU
1.0 to 1.4 p.u. V step 0.01
V1OVTIMDLY
0.0 to 10.0 sec. step 0.01
V1COMP
0 = No; 1 = Yes
V1COMRCH
0.01 to 50.0 W step 0.01 (5A)
0.05 to 250.0 W step 0.05 (1A)
V1COMPINPU
1.0 to 1.4 p.u. V step 0.01
V1COMPTDPU
1.0 to 1.4 p.u. V step 0.01
V1COMPDLY
0.0 to 10.0 sec. step 0.01
FUSEFAIL
0 = No; 1 = Yes
ALL_BELOW
0 = No; 1 = Yes
OUTOFSTEP
0 = No; 1 = Yes
ALL_3_Z2PH
0 = No; 1 = Yes
50G_BLOCK
0 = No; 1 = Yes
Z2TIMETRIP
0 = No; 1 = Yes
Z3TIMETRIP
0 = No; 1 = Yes
Z4TIMETRIP
0 = No; 1 = Yes
Z1PHASTRIP
0 = No; 1 = Yes
ANYZ2PHASE
0 = No; 1 = Yes
CONFGTRIP
0 = No; 1 = Yes
LINEPICKUP
0 = No; 1 = Yes
BYPASSTL3
0 = No; 1 = Yes
I1PICKUP
1.0 to 15.0 A step 0.1
0.2 to 3.0 A step 0.1
REMOTEOPEN
0 = No; 1 = Yes
TL20PICKUP
10 to 100 msec. step 1
LINEOVERLD
0 = No; 1 = Yes
LEVEL1PU
2.5 to 20.0 A step 0.1 (5A)
0.5 to 4.0 A step 0.1 (1A)
LEVEL2PU
5.0 to 40.0 A step 0.1 (5A)
1.0 to 8.0 A step 0.1 (1A)
LEVEL1TDLY
10 to 200 sec. step 1
LEVEL2TDLY
10 to 99 sec. step 1
PICKSCHEME
0 = STEPDST; 1 = PUTT;
2 = POTT1; 3 = POTT2;
4 = HYBRID
NUMRCVR
0, 1, 2
LPS-D Line Protection System
B.1 MEMORY MAPPING
R/W
Format
Code
R/W
Float
R/W
INT
R/W
Float
R/W
Float
R/W
Float
R/W
INT
R/W
Float
R/W
Float
R/W
Float
R/W
Float
R/W
INT
R/W
INT
R/W
INT
R/W
INT
R/W
INT
R/W
INT
R/W
INT
R/W
INT
R/W
INT
R/W
INT
R/W
INT
R/W
INT
R/W
INT
R/W
Float
R/W
INT
R/W
INT
R/W
INT
R/W
Float
R/W
Float
R/W
Float
R/W
Float
R/W
INT
R/W
INT