Certification
6.2 EMC and Environmental Type Tests
•
6.2
EMC and Environmental Type Tests
The RUGGEDCOM RSG2488 has passed the following EMC and environmental tests.
EMC Type Test for IEC 61850-3
Note
•
•
•
IEC 61000-4-2
IEC 61000-4-3
IEC 61000-4-4
IEC 61000-4-5
IEC 61000-4-6
IEC 61000-4-8
40
IEC 61000-6-2
Electromagnetic Compatibility (EMC) – Part 6-2: Generic Standards – Immunity
for Industrial Environments
In the case of an all fiber port configuration, this product meets all Class 2
requirements. Otherwise, all Class 1 requirements are met for copper ports.
If the unit contains copper ports, the IEC 1613 conformance is Class 1, during
which disturbance errors may occur but recovery is automatic.
If the unit contains all fiber ports, the IEC1613 conformance is Class 2, during
which no disturbance errors will occur.
Test
ESD
Radiated RFI
Burst (Fast
Transient)
Surge
Induced
(Conducted) RFI
Magnetic Field
Description
Enclosure Contact
Enclosure Air
Enclosure Ports
Signal Ports
DC Power Ports
AC Power Ports
Earth Ground Ports
Signal Ports
DC Power Ports
AC Power Ports
Signal Ports
DC Power Ports
AC Power Ports
Earth Ground Ports
Enclosure Ports
Test Levels
Severity Levels
± 8 kV
± 15 kV
20 V/m
± 4 kV @ 2.5
and 5 kHz
± 4 kV @ 2.5
and 5 kHz
± 4 kV @ 5 kHz
± 4 kV Line-
to-Earth
± 2 kV Line-to-Line
± 2 kV Line-
to-Earth, ± 1
kV Line-to-Line
± 4 kV Line-
to-Earth
± 2 kV Line-to-Line
10 V
100 A/m for 3 min
1000 A/m for 3 s
RUGGEDCOM RSG2488
Installation Manual, 07/2021, C79000-G8976-1048-11
4
a
Note
4
3
4
3
5