Connecting The Failsafe Alarm Relay - Siemens RUGGEDCOM RSG2488 Installation Manual

Rugged ethernet switches
Hide thumbs Also See for RUGGEDCOM RSG2488:
Table of Contents

Advertisement

Installing the Device
2.4 Connecting the Failsafe Alarm Relay
To mount the device to a panel, do the following:
1.
2.
2.4

Connecting the Failsafe Alarm Relay

The failsafe relay can be configured to latch based on alarm conditions. The NO
(Normally Open) contact is closed when the unit is powered and there are no active
alarms. If the device is not powered or if an active alarm is configured, the relay
opens the NO contact and closes the NC (Normally Closed) contact.
Note
Control of the failsafe relay output is configurable through RUGGEDCOM RSG2488 .
One common application for this relay is to signal an alarm if a power failure occurs.
For more information, refer to the RUGGEDCOM ROS Configuration Manual for the
RUGGEDCOM RSG2488.
The following shows the proper relay connections.
12
Place the device against the panel and align the adapters with the mounting
holes.
1
1
Screw
1
Panel/DIN Rail Adaptor
2
Figure 2.4
Panel Mounting
Install the supplied screws to secure the adapters to the panel.
2
RUGGEDCOM RSG2488
Installation Manual, 07/2021, C79000-G8976-1048-11