Blanking Mode In The Basic Configuration - Pilz PSEN op4F-A Series Operating Manual

Safety light curtain
Table of Contents

Advertisement

OPERATING MANUAL
7.9.7

Blanking mode in the basic configuration

Only a reduced series of configurations can be implemented in basic configuration mode.
1 fixed blanking zone
2 fixed blanking zones
• 1 fixed blanking zone: only 1 zone can be configured as a blanking zone.
• 2 fixed blanking zones: 2 zones can be configured as blanking zones.
Floating blanking disabled
Floating blanking 1 beam (with
partial surveillance)
Floating blanking 2 beams (with
partial surveillance)
Reduced resolution 4
• Floating blanking disabled: Floating blanking is not permitted.
• 1 floating blanking beam: The light curtain remains in NORMAL OPERATION if 1 beam
or 0 beams are interrupted.
• 2 floating blanking beams: The light curtain remains in NORMAL OPERATION if 2
adjacent beams, 1 beam or 0 beams are interrupted.
• Reduced resolution 4: The light curtain switches to a SAFE state if more than 4
adjacent beams are interrupted.
64
BCM configuration: Fixed blanking
LED 8 ON green
LED 8 OFF
BCM configuration: Floating blanking
LED 6 ON green
LED 7 ON green
LED 6 ON green
LED 7 OFF
LED 6 OFF
LED 7 ON green
LED 6 OFF
LED 7 OFF
PSEN op4F/H-A series
LEVEL
LEVEL
1003067-EN-04