Preface This document is the original document. All rights to this documentation are reserved by Pilz GmbH & Co. KG. Copies may be made for the user's internal purposes. Suggestions and comments for improving this documenta- tion will be gratefully received.
Attach the safety light curtain to the mounting surface ............. Orientation ..........................General guidelines........................Safety light curtain alignment....................Wiring ............................General guidelines........................Connector pin assignment ......................Earthing the safety light curtain ....................Commissioning ........................System connection ........................Checking the safety light curtain....................Operating Manual PSEN opII3B Series 1004845-EN-02...
Page 4
Order reference for safety light curtains ................... Order reference for accessories ....................Mirror column set ........................Mirror columns .......................... Protective column sets......................Protective columns ........................Order reference: Component parts................... Appendix ..........................Check list ..........................EC declaration of conformity ....................Operating Manual PSEN opII3B Series 1004845-EN-02...
PSEN opII3B Series Introduction Validity of documentation This documentation is valid for the product PSEN opII3B Series from Version 1.0. This operating manual explains the function and operation, describes the installation and provides guidelines on how to connect the product.
Overview Safety light curtains of the PSEN opII3B Series are electrosensitive protective equipment (ESPE type 3) in accordance with DIN EN 61496-1 for work areas in which machines, ro- bots, and automated systems could endanger the physical integrity of operators.
Page 7
– Protected field heights of 750 mm – 1200 mm, including: 1 PSEN opII Adv Bracket Kit3 (= 3 clamping units per transmitter and receiver) – Protected field heights of 1350 mm – 1500 mm, including: 2 PSEN opII Adv Bracket Kit2 (= 4 clamping units per transmitter and receiver) Operating Manual PSEN opII3B Series 1004845-EN-02...
Fig.: Front view of the safety light curtain transmitter and receiver, protected field height 450 ‑ 1500 mm with connection cable and installation kit Legend [1] Protected field height [2] Effective protected field height [3] Tinted front panel Operating Manual PSEN opII3B Series 1004845-EN-02...
Holder for connecting the transmitter/receiver end caps to the flexible bracket Tightening screw M3x33.4 oval-head screw, self-tapping Clamping screw with ISO 4762 M4x10 8.8 cylinder screw with nut Mounting screw ISO 4762 M6x20 8.8 cylinder screw with washer Operating Manual PSEN opII3B Series 1004845-EN-02...
PSEN opII3B Series Safety Intended use Safety light curtains in the PSEN opII3B Series are electrosensitive protective equipment of the ESPE type 3. They are used to protect personnel and systems. The safety light curtains are designed to Secure danger zones within buildings and Secure access within buildings with the following resolution: –...
In safety-related applications, please comply with the mission time T in the safety-related characteristic data. When decommissioning, please comply with local regulations regarding the disposal of electronic devices (e.g. Electrical and Electronic Equipment Act). Operating Manual PSEN opII3B Series | 11 1004845-EN-02...
[ of the safety light grid. The safety light grid in the PSEN opII3B Series offers the following functions: Automatic start automatic restart Operation of 2 safety light grids that are parallel to one another and are installed with the...
Page 13
Check is begun to determine whether the protected field is clear and whether there are faults Response time (coded/uncoded), until OSSDs switch to the OFF state (see Technical details [ 42]) Minimum time that the OSSDs remain in the OFF state: 80 ms Operating Manual PSEN opII3B Series | 13 1004845-EN-02...
Time between the OSSDs changing to the OFF state and the hazardous machine move- ment stopping (including the reaction time of the connected relay) Approach speed The speed with which the object to be detected is nearing the danger zone in mm/s Operating Manual PSEN opII3B Series | 14 1004845-EN-02...
Avoid strong electromagnetic interference when operating the safety light grid. When operating the safety light grid, avoid the development of smoke, mist, or dust that would reduce the grid’s operating range. Operating Manual PSEN opII3B Series | 15 1004845-EN-02...
As a result, the safety light grid must be installed at a minimum distance from reflective sur- faces. Fig.: Interference with the function of the safety light curtain due to reflective surfaces – top view Operating Manual PSEN opII3B Series | 16 1004845-EN-02...
Page 17
The formula for calculating the minimum distance D is: For a working distance of less than 3 m: D = 0.131 m For a working distance of 3 m or more: D = working distance in m x tan ⍺ Operating Manual PSEN opII3B Series | 17 1004845-EN-02...
[ 16]. Without beam coding Legend Transmitter from the first safety light curtain Receiver from the first safety light curtain Transmitter from the second safety light curtain Operating Manual PSEN opII3B Series | 18 1004845-EN-02...
Page 19
[2] ≥ 2.5 m and [3] ≥ 2.5 m 300 mm resolution [2] < 10 m or [3] < 10 m 2 x 10 m x tan α [2] ≥ 10 m and [3] ≥ 10 m Operating Manual PSEN opII3B Series | 19 1004845-EN-02...
If several adjacent safety light curtains need to be installed, steps must be taken to ensure that the transmitter on one safety light curtain does not interfere with the receiver on an- other safety light curtain. Operating Manual PSEN opII3B Series | 20 1004845-EN-02...
Please consider this reduction when positioning the safety light curtain. You should not use more than two mirrors per device. Any dust or dirt on the mirror’s reflective surface will drastically reduce the operating range. Operating Manual PSEN opII3B Series | 21 1004845-EN-02...
The optical surfaces of the transmitter and receiver must be parallel to each other and ori- ented opposite to each other. The connection sides of the transmitter and receiver must be on the same side and at the same height (see diagram). Operating Manual PSEN opII3B Series | 22 1004845-EN-02...
[1]: If the standard installation kit is used, the gap [2] between the safety light curtain [1] and the installation surface [3] must be smaller than the safety light curtain resolution. Operating Manual PSEN opII3B Series | 23 1004845-EN-02...
Page 24
Ensure that the holder is flush with the end cap (see diagram). Attach the holder to the end cap with the tightening screws included in delivery. [1] Torque setting 0,7 Nm Operating Manual PSEN opII3B Series | 24 1004845-EN-02...
Page 25
The flexible bracket [3] must be seated on one side of the holder [2]. Bore holes in the installation surface (two M6 screw boreholes per flexible bracket) for mounting the flexible brackets for the transmitter and receiver. Operating Manual PSEN opII3B Series | 25 1004845-EN-02...
Orientation with a laser orientation aid: the safety light curtain need not be switched on Orientation without a laser orientation aid: the safety light curtain must already be wired (see chapter entitled "Wiring" in the safety curtain’s operating manual) and must be switched on Operating Manual PSEN opII3B Series | 26 1004845-EN-02...
[2] Horizontal: by moving up and down in the slots in a horizontal direction [3] The axis orientation can be changed by rotating the flexible bracket right or left Pilz recommends that modifications to the orientation of the transmitter/receiver be made in the following sequence: 1.
Page 28
Tighten the clamping screws [1] and the nuts [2] on the flexible bracket to a torque of 1,1 Tighten the brackets’ mounting screws [3] on the installation surface to a torque of 3 Nm. Legend [1] Clamping screw [2] Nut [3] Mounting screws Operating Manual PSEN opII3B Series | 28 1004845-EN-02...
5-pin connector on the transmit- Assignment Cable colour uncoded: +24 VDC brown A-coded: +24 V DC B-coded: 0 V DC Reserved white 0 VDC blue Reserved black uncoded: +24 VDC grey A-coded: 0 V DC B-coded: +24 V DC Operating Manual PSEN opII3B Series | 29 1004845-EN-02...
For PELV power supplies Connect the power supply circuit to the earth conductor. Commissioning System connection Make sure that the selected evaluation device has the following properties: 2-channel with feasibility monitoring OSSD signals are evaluated Operating Manual PSEN opII3B Series | 30 1004845-EN-02...
Page 31
PSEN opII3B Series A test pulse lasting no longer than 300 µs is bridged Suitable Pilz evaluation devices are, for example: PNOZelog for monitoring safety light curtains PNOZsigma for monitoring safety light curtains PNOZ X for monitoring safety light curtains PDP67 ION and PDP67 ION HP –...
CAUTION! When considering the examples, please note that Pilz accepts no respons- ibility for the specific application. In particular, they may not be used without testing and approval. The system manufacturer is responsible for creating appropriate safety con- cepts for the overall plant and for connection to the programmable safety system (including the user program).
Page 33
The danger zone must be secured so that it is impossible to access by circumventing the protected field. Protected field perimeters The protected field perimeters (see Dimensions [ 41]) must completely secure the hazardous area, making it inaccessible. Operating Manual PSEN opII3B Series | 33 1004845-EN-02...
Device status Reception quality: – III: Best quality OSSD status (protected field LED) – I: Worst quality Status of the beam coding when the protected field is interrupted LED indicator on the receiver Operating Manual PSEN opII3B Series | 34 1004845-EN-02...
Ready for operation Green Green The current reception quality status is indicated Safety light curtain is started. The safety light curtain is not Green Green Green Green aligned. Protected field is interrupted, Uncoded Green Operating Manual PSEN opII3B Series | 35 1004845-EN-02...
Page 36
Overtemperature; OSSD in the OFF state Green 1. Ensure that the ambient tem- perature corresponds to the in- formation in the Technical details [ 42]. Restart [ the safety light curtain. Operating Manual PSEN opII3B Series | 36 1004845-EN-02...
Page 37
Undervoltage; OSSD in the OFF state 1. Ensure that the supply voltage cor- green responds to the information in the Technical details [ 42]. 2. Perform a safety light curtain restart [ 38]. Operating Manual PSEN opII3B Series | 37 1004845-EN-02...
Regular checks can bring to light changes to the plant/machine, safeguards and ambient conditions. Regular check Pilz recommends that the safety light curtain be checked every six months. Check the safety light curtain’s front panel. – Scratched front panel: Replace the safety light curtain.
The exchange of components of the safety light curtain A changed connection of the safety light curtain (change from uncoded connection to coded connection). You must comply with the requirements of the applicable national regulations. Operating Manual PSEN opII3B Series | 39 1004845-EN-02...
Moist cotton cloths should be used for cleaning. Avoid using Alcohol, Solvents, Cloths made of wool, Cloths made of synthetic material. Clean the lens covers during the regular check of the safety light curtain [ 38]. Operating Manual PSEN opII3B Series | 40 1004845-EN-02...
Fig.: Front view of safety light curtain with 170 mm resolution, transmitter and receiver, protected field height 450 – 1500 mm with connection cable Legend [1] Total length of transmitter (without cable) [2] Light beams Operating Manual PSEN opII3B Series | 41 1004845-EN-02...
300 µs Supply interruption before de-energisation 600 µs 600 µs 600 µs Response time t1 5,2 ms 5,2 ms 5,2 ms Response time (with beam coding) 11,7 ms 11,7 ms 11,7 ms Operating Manual PSEN opII3B Series | 42 1004845-EN-02...
Page 43
M12, 5-pin male con- M12, 5-pin male con- M12, 5-pin male con- nector nector nector Max. cable length 50 m 50 m 50 m Material Housing Aluminium Aluminium Aluminium End caps Front screen Operating Manual PSEN opII3B Series | 43 1004845-EN-02...
-25 %/+20 % Residual ripple DC Max. power consumption OSSD in the OFF state 2,5 W 2,5 W 2,5 W Max. voltage OSSD in the OFF state 0,2 V 0,2 V 0,2 V Operating Manual PSEN opII3B Series | 46 1004845-EN-02...
Page 47
Vibration In accordance with the standard EN 60068-2-6 EN 60068-2-6 EN 60068-2-6 Frequency 10 - 150 Hz 10 - 150 Hz 10 - 150 Hz Amplitude 0,75 mm 0,75 mm 0,75 mm Operating Manual PSEN opII3B Series | 47 1004845-EN-02...
Page 48
754 mm Width 35 mm 35 mm 35 mm Depth 40 mm 40 mm 40 mm Weight 1.415 g 1.816 g 2.217 g Where standards are undated, the 2015-12 latest editions shall apply. Operating Manual PSEN opII3B Series | 48 1004845-EN-02...
300 µs Supply interruption before de-energisation 600 µs 600 µs 600 µs Response time t1 5,2 ms 5,2 ms 5,4 ms Response time (with beam coding) 11,7 ms 11,7 ms 11,7 ms Operating Manual PSEN opII3B Series | 49 1004845-EN-02...
Page 50
M12, 5-pin male con- M12, 5-pin male con- M12, 5-pin male con- nector nector nector Max. cable length 50 m 50 m 50 m Material Housing Aluminium Aluminium Aluminium End caps Front screen Operating Manual PSEN opII3B Series | 50 1004845-EN-02...
Safety light curtain for body protection, 632 105 s-170-150 Resolution 170 mm Protected field height 1500 mm PSEN opII3B- Safety light curtain for body protection, 632 110 s-300-045 Resolution 300 mm Protected field height 450 mm Operating Manual PSEN opII3B Series | 52 1004845-EN-02...
750 mm up to and including 1200 mm Laser alignment guide Product type Features Order No. PSEN opII laser Laser orientation aid for safety light curtain from the PSEN opII series 632 014 pointer Operating Manual PSEN opII3B Series | 53 1004845-EN-02...
Page 54
PSEN op cable axial 10 m M12, 5-pin fe- 630 312 M12 5-pole 10m male con- nector, straight PSEN cable 20 m M12, 5-pin fe- 630 298 M12-5sf 20m male con- nector, straight Operating Manual PSEN opII3B Series | 54 1004845-EN-02...
632 008 column-090 Set PSEN opII mirror with PSEN opII mirror column-120 120 cm 632 009 column-120 Set PSEN opII mirror with PSEN opII mirror column-165 165 cm 632 010 column-165 Set Operating Manual PSEN opII3B Series | 55 1004845-EN-02...
632 413 s-300-090 EMIT- Resolution 300 mm Protected field height 900 mm PSEN opII3B- For safety light curtain for body protection, 632 414 s-300-120 EMIT- Resolution 300 mm Protected field height 1200 mm Operating Manual PSEN opII3B Series | 57 1004845-EN-02...
Page 58
RE- Resolution 300 mm CEIVER Protected field height 750 mm PSEN opII3B- For safety light curtain for body protection, 632 453 s-300-090 RE- Resolution 300 mm CEIVER Protected field height 900 mm Operating Manual PSEN opII3B Series | 58 1004845-EN-02...
Have the technical details been met for all the safety light curtain components? Check access to the danger zone Are all access points to the danger zone safeguarded either by safety light curtains or by mechanical safeguards? Operating Manual PSEN opII3B Series | 59 1004845-EN-02...
Page 60
Are the switching elements that are connec- ted to the OSSDs (valves, contactors, etc.) monitored with feedback loops? Does the wiring of the OSSDs match the cir- cuit diagram? Operating Manual PSEN opII3B Series | 60 1004845-EN-02...
European Parliament and of the Council. The complete EC Declaration of Conformity is available on the Internet at www.pilz.com/downloads. Authorised representative: Norbert Fröhlich, Pilz GmbH & Co. KG, Felix-Wankel-Str. 2, 73760 Ostfildern, Germany Operating Manual PSEN opII3B Series...
Need help?
Do you have a question about the PSEN opII3B Series and is the answer not in the manual?
Questions and answers