PNOZ ms2p TTL
Configurable safety systems PNOZmulti
}
Operating Manual-1001722-EN-03

Advertisement

Table of Contents
loading

Summary of Contents for Pilz PNOZ ms2p TTL

  • Page 1 PNOZ ms2p TTL Configurable safety systems PNOZmulti Operating Manual-1001722-EN-03...
  • Page 2 Preface This document is a translation of the original document. All rights to this documentation are reserved by Pilz GmbH & Co. KG. Copies may be made for internal purposes. Suggestions and comments for improving this documentation will be gratefully received.
  • Page 3: Table Of Contents

    Connect incremental encoder to the speed monitor via an adapter Connection of proximity switches and incremental encoder 6.5.1 Proximity switch and incremental encoder on various axes 6.5.2 Proximity switch and incremental encoder on one axis Operating Manual PNOZ ms2p TTL 1001722-EN-03...
  • Page 4 Connection of an incremental encoder and proximity switch on an axis Section 7 Operation LED indicators Signal statuses Faults - malfunctions Section 8 Technical details Safety characteristic data Section 9 Order reference Product Accessories Section 10 Application Examples Operating Manual PNOZ ms2p TTL 1001722-EN-03...
  • Page 5: Operating Manual Pnoz Ms2P Ttl

    Introduction Introduction Validity of documentation This documentation is valid for the product PNOZ ms2p TTL (Coated Version). It is valid until new documentation is published. This operating manual explains the function and operation, describes the installation and provides guidelines on how to connect the product.
  • Page 6 Introduction INFORMATION This gives advice on applications and provides information on special fea- tures. Operating Manual PNOZ ms2p TTL 1001722-EN-03...
  • Page 7: Overview Scope

    Scope Expansion module PNOZ ms2p TTL (Coated Version) Jumper Unit features Using the product PNOZ ms2p TTL (Coated Version): Speed monitor for connection to a base unit from the configurable control system PNOZmulti The product has the following features: Monitoring of 2 independent axes Connection per axis –...
  • Page 8: Front View

    X22: – female connector for the connection of an incremental encoder at axis 2 LEDs: – POWER – FAULT – SHAFT 1 – SHAFT 2 – – Operating Manual PNOZ ms2p TTL 1001722-EN-03...
  • Page 9: Safety

    For applications in accordance with PL e and SIL CL 3, the "Overspeed" output must be integrated into the safety function in every operating mode and evaluated so that a shutdown occurs if the output switches to a safe condition ("Overspeed" output = "0"). Operating Manual PNOZ ms2p TTL 1001722-EN-03...
  • Page 10: System Requirements

    Hazards that can arise through an automatic restart must be excluded within the user program. The coated version of the product PNOZ ms2p TTL (Coated Version) is suitable for use where there are increased environmental requirements (see Technical details [ 29]).
  • Page 11: Safety Regulations

    In safety-related applications, please comply with the mission time T in the safety-re- lated characteristic data. When decommissioning, please comply with local regulations regarding the disposal of electronic devices (e.g. Electrical and Electronic Equipment Act). Operating Manual PNOZ ms2p TTL 1001722-EN-03...
  • Page 12: For Your Safety

    Do not open the housing or make any unauthorised modifications. Please make sure you shut down the supply voltage when performing maintenance work (e.g. exchanging contactors). Operating Manual PNOZ ms2p TTL 1001722-EN-03...
  • Page 13: Function Description

    Incremental encoders and/or proximity detectors can be used to record the values. The configuration of the speed monitor is described in detail in the PNOZmulti Configur- ator's online help. Block diagram RJ45 RJ45 Operating Manual PNOZ ms2p TTL 1001722-EN-03...
  • Page 14: Input Device Types

    Incremental encoders 4.4.2.1 Requirements of the incremental encoders Only incremental encoders with a differential output of the following type are permitted – Sin/Cos – TTL (RS422) Please note the values stated in the technical details Operating Manual PNOZ ms2p TTL 1001722-EN-03...
  • Page 15: Adapter For Incremental Encoders

    The adapter records the data between the encoder and drive and makes it available to the PNOZ ms2p TTL (Coated Version) via the RJ45 socket. Pilz supplies complete adapters as well as ready-made cable with RJ45 connector, which can be used when making your own adapter. The range of products in this area is con- stantly being expanded.
  • Page 16: Installation

    Damage due to electrostatic discharge! Electrostatic discharge can damage components. Ensure against discharge before touching the product, e.g. by touching an earthed, conductive sur- face or by wearing an earthed armband. Dimensions 94 (3.70") (1.77") Operating Manual PNOZ ms2p TTL 1001722-EN-03...
  • Page 17: Connecting The Base Unit And Expansion Modules

    Please refer to the document "PNOZmulti System Expansion" for details of the number of modules that can be connected to the base unit and the module types. Operating Manual PNOZ ms2p TTL 1001722-EN-03...
  • Page 18: Commissioning

    1 incremental encoder 2 proximity switches 1 incremental encoder and 1 proximity switch Incremental encoder Proximity switch Connection axis 1 I10, I11, 0 V I10, 0 V Connection axis 2 I20, I21, 0 V I20, 0 V Operating Manual PNOZ ms2p TTL 1001722-EN-03...
  • Page 19: Pin Assignment Of Rj45 Socket

    The proximity switch must always be connected to a 0 V terminal of the speed monitor. The 0 V terminals are connected internally. Connect proximity switch to 24 VDC of the power supply or the speed monitor (the 24 V terminals of the speed monitor are connected internally) Operating Manual PNOZ ms2p TTL 1001722-EN-03...
  • Page 20: Connection Of The Incremental Encoder

    The signals relevant for the speed monitor are utilised in parallel by the adapter. The in- formation stated under "Connect incremental encoder signals to the speed monitor" and in the adapter operating manual must be observed when connecting the supply voltage. Supply only incremental encoder with 5 VDC. Operating Manual PNOZ ms2p TTL 1001722-EN-03...
  • Page 21 Adapter Incremental Drive 5 V DC encoder Speed monitor Fig.: Connection via adapter and drive Adapter Incremental 5 V DC encoder Speed monitor Fig.: Connection via adapter Operating Manual PNOZ ms2p TTL 1001722-EN-03...
  • Page 22: Connection Of Proximity Switches And Incremental Encoder

    Proximity switch and incremental encoder on various axes Axis 1: Proximity switch at I10, I11 incremental encoder at X12 Axis 2: Proximity switch at I20, I21 incremental encoder at X22 Fig.: Proximity switch and incremental encoder on various axes Operating Manual PNOZ ms2p TTL 1001722-EN-03...
  • Page 23 Proximity switch at I10 (I11 is unused) Incremental encoder at X12 Axis 2: Proximity switch at I20 (I21 is unused) Incremental encoder at X22 Axis 1 Axis 1 Fig.: Proximity switch and incremental encoder on one axis Operating Manual PNOZ ms2p TTL 1001722-EN-03...
  • Page 24: Connection Examples

    6.6.1 Connection of 2 proximity switches and an incremental encoder Description 2 proximity switches, pnp-switching 1 incremental encoder Speed monitor Incremental Encoder Drive PNOZ msi15p Fig.: Connection of 2 proximity switches, pnp-switching, one incremental encoder Operating Manual PNOZ ms2p TTL 1001722-EN-03...
  • Page 25: Connection Of 4 Proximity Switches

    Connection of 4 proximity switches Description 4 proximity switches, pnp-switching Connection through 24 V terminals and 0 V Speed monitor Fig.: Connection of 4 proximity switches, pnp-switching, connection through 24 V terminals and 0 V Operating Manual PNOZ ms2p TTL 1001722-EN-03...
  • Page 26 1 proximity switch, pnp-switching 1 incremental encoder Incremental encoder and proximity switch on one axis Speed monitor Incremental encoder Drive PNOZ msi15p Fig.: Connection of an incremental encoder and proximity switch, pnp-switching, on an axis Operating Manual PNOZ ms2p TTL 1001722-EN-03...
  • Page 27: Operation

    The LEDs “POWER”, “DIAG”, “FAULT”, “IFAULT” and “OFAULT” will light up on the base unit. The PNOZmulti safety system is ready for operation when the "POWER" and "RUN" LEDs on the base unit and the "READY" LED on the PNOZ ms2p TTL (Coated Version) are lit continuously. LED indicators...
  • Page 28: Signal Statuses

    Monitoring the direction of rotation: If an internal error occurs or there is an error due to a defective incremental encoder ("FAULT" LED illuminates or flashes), an incorrect direction of rotation may be signalled for approx. 500 ms. Operating Manual PNOZ ms2p TTL 1001722-EN-03...
  • Page 29: Technical Details

    With hysteresis 0.2 Hz - 500 kHz 0.2 Hz - 500 kHz Times 773811 773816 Configurable switch-off delay 0 - 2.500 ms 0 - 2.500 ms Supply interruption before de-ener- 20 ms 20 ms gisation Operating Manual PNOZ ms2p TTL 1001722-EN-03...
  • Page 30 In accordance with the standard EN 60529 EN 60529 Mounting area (e.g. control cab- IP54 IP54 inet) Housing IP20 IP20 Terminals IP20 IP20 Mechanical data 773811 773816 Mounting position Horizontal on top hat rail Horizontal on top hat rail Operating Manual PNOZ ms2p TTL 1001722-EN-03...
  • Page 31: Safety Characteristic Data

    3,68E-09 SIL 3 4,84E-05 Incremental encoder PL e Cat. 3 SIL CL 3 6,73E-09 SIL 3 8,18E-05 All the units used within a safety function must be considered when calculating the safety characteristic data. Operating Manual PNOZ ms2p TTL 1001722-EN-03...
  • Page 32 A safety function's SIL/PL values are not identical to the SIL/PL values of the units that are used and may be different. We recommend that you use the PAScal software tool to calculate the safety function's SIL/PL values. Operating Manual PNOZ ms2p TTL 1001722-EN-03...
  • Page 33: Order Reference

    KOP-XE coated Jumper, coated version 774 640 Connection terminals Product type Features Order no. Set spring terminals 1 set of spring-loaded terminals 783 800 Set screw terminals 1 set of screw terminals 793 800 Operating Manual PNOZ ms2p TTL 1001722-EN-03...
  • Page 34: Application Examples

    If the "Overspeed" output (see red marking) = "0", either the maximum permitted speed has been exceeded or the speed monitor has recognised a fault. "Overspeed" output = "0" must lead to the shutdown of the relevant axis. Operating Manual PNOZ ms2p TTL 1001722-EN-03...
  • Page 35 If the "Overspeed" output (see red marking) = "0", either the maximum permitted speed has been exceeded or the speed monitor has recognised a fault. "Overspeed" output = "0" must lead to the shutdown of the relevant axis, irrespective of whether the "reduced speed" operating mode is active. Operating Manual PNOZ ms2p TTL 1001722-EN-03...
  • Page 36 Front cover Support Technical support is available from Pilz round the clock. Americas Australia Scandinavia Brazil +61 3 95600621 +45 74436332 +55 11 97569-2804 Spain Canada Europe +34 938497433 +1 888-315-PILZ (315-7459) Austria Switzerland +41 62 88979-30 Mexico +43 1 7986263-0...