Installation And Configuration; Mounting - Mitel CPDM3 Installation Manual

Table of Contents

Advertisement

Installation Guide

4. INSTALLATION AND CONFIGURATION

The hardware can be mounted vertically on a wall or be placed horizontally in a 19"
rack. It must be fixed by screws or other fixtures to the wall or rack, and must not be
easily movable.
Figure 5. Recommended installation and configuration procedure
Mount the
hardware

4.1 MOUNTING

4.1.1 ENVIRONMENTAL
The hardware shall be placed in an environment with an ambient temperature between
0°C to +40°C (32°F to 104°F). Relative humidity: 30 - 85% RH (non condensing).
4.1.2 WALL MOUNTING
Four screws size 3.5×40 mm (0.14×1.6 in) together with four wall plugs and four
screws size M3×6 mm (0.12×0.24 in), are delivered with the product. The M3×6 screws
are used for attaching the assembly brackets to the module. Use the 3.5×40 mm
(0.14×1.6 in) screws for walls made of wood. For walls made of concrete and bricks
use them together with the wall plugs. For other types of walls use suitable screws and
plugs according to wall material.
IMPORTANT: When mounted on a wall, it is of great importance that the connections
1
Fasten the supplied assembly brackets on the bottom side of the hardware.
2
Use the supplied screws and wall plugs (or other suitable screws and plugs
dependent on wall material) and mount the hardware as shown in
Figure 6. Mounting on a wall
34/1531-ANF901 43 B1 2016-03-31
Connect the
Access the
supply voltage
application
are located in a vertical plane.
Connect
Basic
to required
configuration
equipment
Figure
TD
6.