Bender ISOMETER iso415R Manual page 26

Insulation monitoring device for unearthed 3(n)ac, ac and dc systems (it systems)
Hide thumbs Also See for ISOMETER iso415R:
Table of Contents

Advertisement

Modbus settings
Address
Register name
(dec)
Function 7: Reset
60000 Function selection
60001 Pattern value part 1
60002 Pattern value part 2
60003 Type of reset
26
iso415R-x_D00401_00_M_XXEN / 04.2021
Data type
Bytes Mode
Uint16
2
WO
Uint16
2
WO
Uint16
2
WO
Uint16
2
WO
Value/Unit/Comment
7 → Selection of "Reset" function
13623 → Safety pattern must be written
for the function to be executed
0 → Safety pattern must be written for the
function to be executed
1 → Reset of the alarm message when
fault memory is enabled
Factory
setting
N/A
N/A
N/A