Modbus settings
Address
Register name
(dec)
Alarm behaviour (33200
33200
Start with alarm
33201
Fault memory
Time behaviour (33300
33300
Response delay
33301
Delay on release
33302
Start-up delay
Monitoring functions (33400
33400
Connection monitoring L1/L2 Uint16
Device error codes (58000...58999)
58000
Number of device errors
58001
E-KE connection fault
58002
L1/L2 connection fault
58003
Error firmware version too old Uint16
58004
Error no firmware information Uint16
58005
Error measurement technol-
ogy timeout (C
too high or
e
disturbances in the system)
58006
Calibration error
58007
Write protection error
58008
Read protection error
58009
Error measurement technol-
ogy HW
58010
Error internal voltage 24 V
58011
Error internal voltage 3.5 V
58012
Error internal voltage V
58013
Error RAM microcontroller
(59000...59999)
Control commands
59000
NFC
59001
Relay test
24
iso415R-x_D00401_00_M_XXEN / 04.2021
Data type
...33299
)
Uint16
Uint16
...33399
)
Uint16
Uint16
Uint16
...33499
)
Uint16
Uint16
Uint16
Uint16
Uint16
Uint16
Uint16
Uint16
Uint16
Uint16
3.3 V Uint16
ref
Uint16
Uint16
Uint16
Bytes Mode
Value/Unit/Comment
2
RW
0 = Disabled
1 = Enabled
2
RW
0 = Disabled
1 = Enabled
2
RW
0...1800 [s], step size 1 s
2
RW
0...1800 [s], step size 1 s
2
RW
0...1800 [s], step size 1 s
2
RW
0 = Disabled
1 = Enabled
2
RO
Number of active device errors
2
RO
Error code = 30
2
RO
Error code = 40
2
RO
Error code = 321
2
RO
Error code = 325
2
RO
Error code = 405
2
RO
Error code = 600
2
RO
Error code = 631
2
RO
Error code = 651
2
RO
Error code = 820
2
RO
Error code = 843
2
RO
Error code = 846
2
RO
Error code = 849
2
RO
Error code = 920
2
RW
0 = Disabled
1 = Enabled (automatic disabling
after 15 min)
2
RW
0 = Disable relay (automatic return to normal
operating mode after 60 s)
1 = Enable relay (automatic return to normal
operating mode after 60 s)
2 = Relay test inactive (normal operating mode)
Factory
setting
0
0
0
0
0
1
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
Disabled
Relay test
inactive
Need help?
Do you have a question about the ISOMETER iso415R and is the answer not in the manual?
Questions and answers