Modbus settings
5.2
Register table
Address
Register name
(dec)
Device information (0...99)
0
Device name
16
Article number
32
Serial number
48
Manufacturer
64
Application D number
65
Application version number
66
Application build number
67
Boot loader D number
68
Bootloader version number
69
Boot loader build number
70
Device status
Alarm and measured values (999...1999)
999
Number of active alarms
1000
Insulation resistance R
1001
Alarm-1
1002
Alarm-2
1003
Measuring range status R
Monitoring functions (2000...2999)
2000
Alarm-E/KE
2001
Alarm-L1/L2
2002
R_EKE
2003
R_L1L2
Status information (3000...3999)
3000
Test status
3001
Insulation fault location
3002
Measured value
update counter
22
iso415R-x_D00401_00_M_XXEN / 04.2021
Data type
Bytes Mode
String UTF8
32
String UTF8
32
String UTF8
32
String UTF8
32
Uint16
2
Uint16
2
Uint16
2
Uint16
2
Uint16
2
Uint16
2
Uint16
2
Uint16
2
Uint16
2
F
Uint16
2
Uint16
2
Uint 16
2
F
Uint16
2
Uint 16
2
Uint16
2
Uint16
2
Uint16
2
Int16
2
Uint32
4
Value/Unit/Comment
RO
iso415R-24 or iso415R-2
RO
B71602000 (iso415R-24)
B71603000 (iso415R-2)
RO
10 digits e.g.: 2002123456
RO
Bender
RO
704 = D704
RO
xxx = Vx.xx
RO
RO
705 = D705
RO
xxx = Vx.xx
RO
RO
Bit 0 (LSB): NFC - 0 = disabled, 1 = enabled
Bit 1: Potentiometer R
Bit 2: Potentiometer R
Bit 3-15: 0 (reserved)
RO
0...7
RO
0...10000 [kΩ]
RO
0 = No alarm
2 = Alarm, measured value below Ran1
RO
0 = No alarm
2 = Alarm, measured value below Ran2
RO
0 = " " within measuring range 1 kΩ...10 MΩ
1 = "<" below measuring range
2 = ">" measuring range exceeded
RO
0 = No alarm
2 = Alarm, E/KE connection faulty
RO
0 = No alarm
2 = Alarm, L1/L2 coupling faulty
RO
0...1000 [kΩ];
Resistance between terminals E and KE
RO
0...1000 [kΩ];
Resistance between terminals L1 and L2
RO
0 = No active test
1 = Internal test (local)
2 = External test (remote)
RO
0 = Insulation fault cannot be located
100 = Insulation fault mainly at L1(+)
-100 = Insulation fault mainly at L2(-)
RO
0...2
32
- 0 != ext, 1 = ext
an1
- 0 != ext, 1 = ext
an2
Factory
setting
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A