8.1 Failure searching and problem solving schedule
The follow table suggests possible solutions to face possible common detected failures; to solve errors or alarm conditions
visualized by remote user interface, read Control Manual.
Detected failure
Fans are not running
Insufficient airflow
Insufficient
heating/cooling
performance
Condensate discharge failed
9 – M
D
ATERIAL
ISPOSAL
At the end of unit's lifetime, its components must be dismantled and disposed of respecting the operational regulations
present in its country of installation.
The main materials used for building the unit are :
Precoated galvanized steel sheet metal
-
Galvanized steel sheet metal
-
Aluminum
-
-
Copper
-
Polyester
Polyethylene
-
Glass wool
-
-
Plastic
During disconnection of the unit, avoid gas leakage or liquid spillage on environment, especially if the water has additives
like glycol. For dismissing and disposal, deliver the units to specialized centers according to your national laws.
AERAULIQA SRL
Registered office: via Mario Calderara 39/41, 25018 Montichiari, Brescia
Warehouse - Offices: via Mario Calderara 39/41, 25018 Montichiari, Brescia
Tel 030 674681 fax 030 6872149
www.aerauliqa.com
MIUM0018_REV06_ QRCE_20180312-MIUM-ENG-AQ
Possible reason
No power supply
Electrical connections wrong or loose
Thermal protection on
Fan speed signal missing
Air filter dirty
Air duct clogged
Fan signal too low
Temperature setpoint not right
Heat transfer fluid rate not right
Heat transfer fluid temperature not
right
Airflow too low
Defrost mode on
Discharge point clogged
Drain trap missing or not suitable
ENG
Possible solution
Switch on power supply
Restore
the
right
connections
Check the input current
Check
signal
connection
setting
Replace filter
Check air plant (dampers closed ?)
Adjust fan signal
Adjust temperature setpoint
Ensure the right fluid rate
Ensure the right fluid temperature
See above
Wait for defrost cycle end
Vacate the discharge point
Install suitable drain trap
AQ_001523_02_0721
electrical
and
25

Hide quick links:

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the QRCE Series and is the answer not in the manual?

Questions and answers

This manual is also suitable for:

Qrce 500Qrce 1000Qrce 1500Qrce 2000Qrce 3000Qrce 4000

Table of Contents