METASYS POINT MAPPING TABLES
Some Metasys software use an object number range from 1 to 255. Other Metasys software
use the range 0 to 254. The second type software will interpret object number 1 as 0, 2 as
1, and so on. To access the proper point with that type Metasys software, subtract 1 from
each NPA number in these tables.
The default values on the following pages are shown in BOLD.
Any point not listed on the following pages is reserved for future use.

Analog Inputs (AI)

NPT
NPA
UNIT
AI
1
%
AI
2
Hz, rpm
AI
3
Par. 416
AI
4
Hz
AI
5
Hz
AI
6
Amp
AI
7
kW
AI
8
HP
AI
9
V
AI
10
V
AI
11
%
AI
12
%
AI
13
V
AI
14
AI
15
mA
AI
16
Hz
AI
17
%
AI
18
C
AI
19
Hour
AI
20
Hour
AI
21
kWh
AI
22
-
AI
23
-
AI
24
-
18
VLT
Appendix A
NOTE
Description
Reference
Reference
Feedback [Unit]
Frequency
Frequency x Scale
Motor current
Power
Power
Motor voltage
DC link voltage
Thermal load motor
Thermal load inverter
Terminal 53 analog
Reserved
Terminal 60 analog
Pulse reference
External reference
Inverter temperature
Operating hours
Hours run
kWh counter
Number of power-ups
Number of over temps
Number of over volts
MG.90.C1.02 - VLT is a registered Danfoss trademark
®
2800 Metasys N2
Range
VLT 2800 PNU
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
515
516
517
518
519
520
522
523
524
525
526
527
529
531
532
533
537
600
601
602
603
604
605

Advertisement