= 0 - +55°C
amb
230 V a.c., 50/60 Hz
2.5 VA
10 V < U < 256 V
DO1. Refrigeration *
DO2. Defrost *
DO3. Refrigeration 2 *
DO4. Alarm, light, rail heat,
fan or comp. fan *
* DO1 and DO2 are 16 A relays. DO3 and DO4 are 8 A relays. Max. load must be kept.
** Gold plating ensures make function with small contact loads
*** UL-approval based on 30000 couplings
Koordineret afrimning
Coordinated defrost
RI8RE3ML 10-2016
INSTRUCTIONS
AK-CC 210A
084B8530
CE (250 V a.c.)
UL *** (240 V a.c.)
10 A Resistive
8 (6) A
5FLA, 30LRA
10 A Resistive
8 (6) A
5FLA, 30LRA
6 A Resistive
6 (3) A
3FLA, 18LRA
131 VA Pilot duty
4 (1) A
4 A Resistive
Min. 100 mA**
131 VA Pilot duty
Data communication
Type: Pt 1000 (1000 Ω /0°C ) /
Ptc 1000 (TYPE) /
NTC-M2020 (5000 Ω / 25°C)
( o06)
LON RS485
MOD-bus

Advertisement

loading

Summary of Contents for Danfoss AK-CC 210A

  • Page 1 INSTRUCTIONS AK-CC 210A 084B8530 = 0 - +55°C 230 V a.c., 50/60 Hz 2.5 VA 10 V < U < 256 V Type: Pt 1000 (1000 Ω /0°C ) / Ptc 1000 (TYPE) / NTC-M2020 (5000 Ω / 25°C) CE (250 V a.c.) UL *** (240 V a.c.)
  • Page 2 — Electrical connections - Conexão elétrica l = max. 15 m *) DI1, DI2: AU: Guld, Gold, Or, Oro Instructions RI8RE3ML © Danfoss 10/2016 AK-CC 210A...
  • Page 3 20 (=off ) Varighed af -d- i displayet 5 min 240 min 30 min Ventilator Ventilatorstop ved udkoblet kompressor Forsinkelse af ventilatorstop 0 min 30 min 0 min Ventilatorstop temperatur (S5) -50.0°C 50.0°C 50.0°C AK-CC 210A Instructions RI8RE3ML © Danfoss 10/2016...
  • Page 4 Status på relæet til kompressorblæser Kan kun indstilles, når reguleringen er stoppet (r12=0) SW = 1.1x **) Kan styres manuelt, men kun når r12 = -1 ***) Med adgangskode 2 begrænses adgangen til disse menuer Instructions RI8RE3ML © Danfoss 10/2016 AK-CC 210A...
  • Page 5 Hvis du får behov for at vende tilbage til de fabriksindstillede værdier, kan det ske således: - Afbryd forsyningsspændingen til regulatoren - Hold den øverste og nederste knap inde samtidig med at du igen tilslutter forsyningsspændingen. AK-CC 210A Instructions RI8RE3ML © Danfoss 10/2016...
  • Page 6 Max. duration of -d- in display 5 min 240 min 30 min Fan stop at cutout compressor Delay of fan stop 0 min 30 min 0 min Fan stop temperature (S5) -50.0°C 50.0°C 50.0°C Instructions RI8RE3ML © Danfoss 10/2016 AK-CC 210A...
  • Page 7 *) Can only be set when regulation is stopped (r12=0) SW = 1.1x **) Can be controlled manually, but only when r12=-1 ***) With access code 2 the access to these menus will be limited AK-CC 210A Instructions RI8RE3ML © Danfoss 10/2016...
  • Page 8 If you need to return to the factory-set values, it can be done in this way: - Cut out the supply voltage to the controller - Keep upper and lower button depressed at the same time as you recon nect the supply voltage Instructions RI8RE3ML © Danfoss 10/2016 AK-CC 210A...
  • Page 9 5 min 240 min 30 min Ventilador Parada do ventilador na desativação do compressor Atraso de parada do ventilador 0 min 30 min 0 min Temperatura de parada do ventilador (S5) -50.0°C 50.0°C 50.0°C AK-CC 210A Instructions RI8RE3ML © Danfoss 10/2016...
  • Page 10 *) Pode ser ajustado somente quando a regulagem estiver parada (r12=0) **) Pode ser controlado manualmente, mas somente quando r12=-1 ***) Com código de acesso 2 o acesso a esses menus será limitado Instructions RI8RE3ML © Danfoss 10/2016 AK-CC 210A...
  • Page 11 Se for necessário retornar aos valores dos ajustes de fábrica, pode ser feito desta maneira: - Desativar a tensão de alimentação para o controlador - Mantenha os dois botões pressionados ao mesmo tempo ao conectar novamente a tensão de alimen- tação AK-CC 210A Instructions RI8RE3ML © Danfoss 10/2016...
  • Page 12 Instructions RI8RE3ML © Danfoss 10/2016 AK-CC 210A...