Baxi 755 Installer's Manual page 9

Remote control inset live fuel effect gas fire
Table of Contents

Advertisement

covering or carpet and the floor is of
a type that is likely to be covered in
such a way in the future then the
distance from the base of the
fireplace opening in the wall to the
floor level should be increased to at
least 160mm. The minimum shelf
height will have to be taken from the
base of the fireplace opening.
4.2.2 To a fireplace incorporating a
metal flue box complying with the
constructional requirements of
BS 715 and BS EN 1856 Part 1. The
dimensions of the flue box must
conform to those shown in figure 2.
4.2.3 A precast concrete or clay flue
block system conforming to BS EN
1858 or BS 1289 with dimensions as
in figure 3 or using a 05654K1 spacer
kit. (Installation Instructions part
number 3003095). The current versions of BS1289 and BS EN 1858 recommend that
there should be an air space or insulation between the flue blocks and the plaster
because heat transfer may cause cracking on directly plastered flues. However, generally
this appliance is suitable for installations under all circumstances unless there is a
history of cracking problems.
Remember that faults such as cracking may be caused by poorly built and restrictive
flues, e.g. mortar extrusions, too many bends, flue heights below three metres,
restrictive terminations etc (See figure 3).
4.2.4 If the fireplace opening is greater than the acceptable dimensions given in this
guide, do not use the back of a fire surround or marble to reduce the opening. This may
cause cracking of the surround back or marble.
4.3
Suitable flues and minimum flue sizes are as follows: -
It should be noted that, as with many appliances, sharp bends or horizontal runs in
metal flues at the top of the system can be a cause of problems in these types of
installation.
225mm x 225mm conventional brick flue.
!
175mm diameter lined brick or stone flue.
!
200mm diameter factory made insulated flue manufactured to the current edition of
!
BS EN 1859 or BS 4543.
175mm diameter flue pipe. See BS6461 Part 1 for suitable materials.
!
©
Baxi Heating U.K. Limited 2006.
INSTALLER GUIDE
Figure 2. Metal flue box
Page 9