Configuring
Value
Diagnostics information
F:
Fault cause
R:
System response
A:
Remedy
22
F:
Mode 0: Slave attempts to write into an incorrect address
R:
Restricted telegram data transfer functions
A:
Select own slave address
23
F:
Logical configuring error: Slave-to-slave communications was configured as duplex
operation, however, only one direction is possible for each slave (send or receive)
R:
Send and receive the same data
A:
Either configure send or receive for slave-to-slave communications
30
F:
Physical data transfer faulted on the SIMOLINK ring
R:
No telegram data transfer
A:
Increase send power (launch power) at one of the subsections, replace medium or
connector
31
F:
CRC error (check sum error), data transfer along the ring faulted
R:
Telegram failure
A:
Increase send power (launch power) at one of the subsections, replace medium or
connector
32
F:
Timeout error in the SIMOLINK ring, bus node signals a fault
R:
No telegram data transfer
A:
FB @SL, evaluates output NDM, beforehand, check node and medium
33
F:
Mode 0: Signaled SIMOLINK cycle time (in the special telegram from SL master)
does not correspond to the configured equivalent sampling time
R:
Restricted telegram data transfer functions
A:
In the HW Config: Adapt the equivalent sampling time of the slave to that of the SL
master
Table 4-14
Error output, SIMOLINK-FBs

4.6.6 Synchronizing individual SIMOLINK rings

NOTE
4-54
When using the FM458-1 DP and the EXM448-2 module, there are
additional ways of synchronizing up to three SIMOLINK masters on a
slave ring that in this case act as clock master. This operating mode is
set-up as follows: For the FM458-1 DP module, the LE bus interrupt of
the leading slave ring (for EXM448-2 is only permitted as the first
interface as master clock) is set as source for the T0 clock cycle - and for
the master interfaces to be synchronized, operating mode 4 or 5 is
selected. In this case, the systems are synchronized almost jitter-free.
When using 2 EXM448-2 connected to an LE bus, only one of the two X1
interfaces of the EXM448-2 can be used as clock master.
The clock cycle of the "clock master" can fail in operation (e.g. if the
leading ring is isolated). This is the reason that measures must be
configured so that when the clock cycle returns, new synchronization to
function block DTS can be initiated.
Application Module FM 458-1 DP - User Manual
A5E01078222-02
Edition 03.2009