2.1.8
Technical data
Order No.
Program memory
Serial service
interface (X1)
Binary inputs (X2)
PROFIBUS DP
interface (X3)
Voltage, currents
Power loss
ambient
temperature
Dimensions
Application Module FM 458-1 DP - User Manual
A5E01078222-02
Edition 03.2009
Application module FM 458-1 DP
Usable MMC-Cards: 2, 4 or 8 MB
RS232 interface (V.24)
Service protocol
Data transfer rate
Number
Electrical isolation
Input voltage
permissible range
nominal voltage
for a 0 signal
for a 1 signal
Input current
for a 0 signal, typical
for a 1 signal, typical
Delay time per channel, max.
Data transfer rate
Nominal voltages at 25 C
+5 V
Battery +3.4V
Power loss, typical
ambient temperature
Assignment, slots
Dimensions W x H x D [mm]
Weight
Product description
6DD1607-0AA1 / 6DD1607-0AA2
DUST1
19.2 kbaud
8
No (only via optional IF modules)
-1 V to +33 V
24 V
-1 V to +6 V or open-circuit inputs
+13.5 V to +33 V
0 mA
3 mA
100 µs
max. 12 Mbaud
Typical current drain
(typical = 2/3 max.)
2.2 A / 1.5 A
15 µA
11 W / 7.5 W
max. 40 C
1
260 x 197 x 20.32
1.0 kg
2-15