Siemens SIMATIC FM 458-1 DP User Manual page 71

Application module
Hide thumbs Also See for SIMATIC FM 458-1 DP:
Table of Contents

Advertisement

Application Module FM 458-1 DP - User Manual
A5E01078222-02
Edition 03.2009
 CTS = FM4581DP.P_B
Connection is connected to the P bus coupling:
CFC entry:
Mark the CTS/righthand mouse key/connection to the operand.
The configured module name (default "FM4581DP") appears in the
selection list for the module to be connected.
 AR / AT = 'channelname.datasetnumber"
Any name (max. 6 characters) and separated by a point, the data
set number, which corresponds to the RECNUM info/data in the
SCF58/59 calls.
Value range:
If several data sets are used, the channel names must be unique,
i.e. they must be different.
 CRR / CRT = 'Text'
Enter the name for the virtual connections are which are combined
to form a data set (telegram).
CFC entry:
Mark the connection / righthand mouse key / connection to
operand "!"
and comprises max. 6 characters.
MOD = R
P-bus communications always operates in the refresh mode.
3. Assigning process quantities to the data set:
Marked block outputs are sent and the inputs are supplied from a
receive data set if they are connected to the data set/telegram via the
dialog box "Insert Connection to Address". All virtual connections with
this name are combined to form a data set.
A sequence number still has to be specified for each value (connection).
This only specifies the sequence of the associated value in the data
set, but not the absolute position!
For the CFC code compilation, the data, associated with a data set,
are arranged in the memory in an increasing sequence. The
sequence numbers can be assigned with gaps, e.g. so that data can
be easily and subsequently inserted..
Contrary to "data transfer with peripheral accesses", for virtual
communications, data is always packed consecutively without any
gaps. The configuring engineer must ensure, by sensibly assigning
the sequence number, that the data are saved to word or double word
limits in order to achieve a high processing speed.
The sequence number does not provide information on the address
and does not specify the offset!
If an offset of a value in the data set (e.g. in bytes) is required for S7
program, it can be calculated from the sum of all of the previously
located values, taking into account their data type (length=2 for INT,
length=4 for REAL/DINT).
2 to 127
for the send and receive data set
Configuring
4-13