4.7.4.4

Configuring the function blocks

Application Module FM 458-1 DP - User Manual
A5E01078222-02
Edition 03.2009
For the "automatic mode, memory card" mode, only the TAB and/or
TAB_D function blocks must be configured, depending as to whether
table values, REAL data type and/or DINT data type have to be
managed. Each table may only contain values of one data type. If several
tables are to manage various data types, then a TAB or TAB_D should
be configured for each table.
The TAB and TAB_D function blocks should be configured in a sampling
time greater than or equal to 32ms. The following connection settings are
required:
CTS=
0
US =
Not assigned
NAM =
Name of the table file (with file name extension which was defined
when "saving", e.g. MS Excel)
AUT =
1 (automatic mode activated)
The configuring is shown in the following diagram:
Fig. 4-58
Configuring the TAB function block
The table function blocks for 2 tables are shown in the following diagram.
The table values, which are now managed by the function blocks, can
now also be used by additional function blocks, e.g. FB TABCAM.
Configuring
4-91