P1" Outdoor Unit: High Voltage Of Capacitor In; Main Inverter Circuit - Daikin RXYSQ4-5-6PA7V1B Service Manual

Vrv iii-s
Table of Contents

Advertisement

Troubleshooting by Indication on the Remote Controller
P1
3.40 "
" Outdoor Unit:
Inverter Circuit
P1
Remote
Controller
Display
Applicable
RXYSQ4~6PA
Models
Method of
Malfunction is detected according to the voltage waveform of main circuit capacitor built in the
inverter.
Malfunction
Detection
Malfunction
When the aforementioned voltage waveform becomes identical with the waveform of the power
supply open phase.
Decision
Conditions
Supposed
Causes
Troubleshooting
188
High Voltage of Capacitor in Main
Defect of main circuit capacitor
Improper main circuit wiring
Defect of outdoor unit PC board (A2P)
Imbalance of phase-to-phase voltages
Open phase
Be sure to turn off power switch before connect or disconnect connector,
Caution
or parts damage may be occurred.
Make measurement of power
supply voltages between L1 and
L2, L1 and L3, and L2 and L3.
Have the
power supply voltages
of three phases fallen within the
range of rated voltage
±10%?
YES
Has the
imbalance of
phase-to-phase voltages
fallen within
±10%?
YES
NO
NO
SiBE34-802
Correct the power supply voltages.
Correct the power supply voltages.
Replace the inverter PC board
assy (A2P).
Troubleshooting