Deutschmann Automation GmbH & Co. KG
The operational sequence is as follows:
The Gateway has to be in the config-mode.
The script-download is initiated with "Ctrl-P (=0x10)".
After that the data follows byte by byte as ASCII-hex-characters.
The download is terminated with a "LF (=0x0A)".
Afterwards the word-checksum follows as ASCII-hex-characters.
The Gateway responds with a clear text reply to that download and carries out a warm start.
Example:
The following 4-bytes script is supposed to be downloaded: 0x01 0x12 0x5A 0x23
The sum of the bytes is 0x0090 as checksum.
Then the following sequence is to be sent:
1.
0x10
Ctrl-P
2.
0x30
'0'
3.
0x31
'1'
4.
0x31
'1'
5.
0x32
'2'
6.
0x35
'5'
7.
0x41
'A'
8.
0x32
'2'
9.
0x33
'3'
10. 0x0A
LF
11. 0x30
'0'
12. 0x30
'0'
13. 0x39
'9'
14. 0x30
'0'
Gateway's reply: "Download ok"
7.4
Configuration of the UNIGATE
®
UNIGATE
IC is delivered with an empty script.
The configuration of the UNIGATE
address.
7.4.1
Ethernet
•
Baud rate: 100 MBaud
•
IP-address (Gateway)
•
Ethernet (MAC-address)
•
IP-destination host
27.11.20
Instruction manual UNIGATE
®
IC
®
IC - PROFINET is restricted to the setting of the Ethernet-
®
IC - PROFINET 1Port V. 3.4
Script and configuration
29