Software
4.2.4

System Program

The system program can be replaced, that is, updated to a newer version, in one of
two ways:
Via PC
or
Via External Memory
Card. See section
Downloading the System
Program in E1012 and E1022
for E1012 and E1022.
Via PC
The configuration tool E-Designer 7 is used to download system programs via a PC
to the operator panel. The transfer can be made via the serial port or over Ethernet.
The serial cable should be a CAB30 cable and the Ethernet cable should be a crossed
CAT5 cable.
Transferring the system program to the operator panel via a PC requires the follow-
ing:
– PC with the configuration tool installed.
– Transfer cable between the PC and the operator panel.
– File with new system program (OPSys_b*.cab).
The transfer is made using the following steps:
By Serial Port
1. Connect the cable between the PC and operator panel.
2. Open a project or create a new project with the desired operator panel type.
3. Select Transfer/Update Operator Terminal System Program.
4. Select the OPSys_b*.cab file.
No settings are required in the operator panel.
Over Ethernet
1. Connect the cable between the PC and operator panel.
2. Set the operator panel to Service menu mode (see the
Mode Switches
section).
3. Enter a valid IP address for the operator panel.
4. Set the operator panel back to Run-mode (see the
Mode Switches
section).
5. Open a project or create a new project with the desired operator panel type.
6. Select Transfer/Update Operator Terminal System Program.
7. Select the OPSys_b*.cab file.
8. Select Settings/Use TCP/IP transfer.
9. Enter the operator panel's IP address.
Mitsubishi Electric, MA00758A