Rexroth IndraControl VAM 10.2/40.2 Machine Control Panels
Power routing 230 V
Interfering AC voltage components such as the ones resulting from an uncon‐
trolled three-phase bridge circuit without smoothing and with a ripple factor
(see DIN 40110/10.75, section 1.2) of 5 % are allowed.
That results in the greatest absolute value of 30.2 V as upper voltage limit.
The lowest absolute value of 18.5 V is the lower voltage limit.
1.05 x 28.8 V = 30.2 V
Upper limit
28.8 V
0.866 x 30.2 V = 26.1 V
1.05 x 20.4 V = 21.4 V
Lower limit
20.4 V
0.866 x 21.4 V = 18.5 V
Fig. 8-4:
Limit values of the DC 24 V voltage
min. 16 mm ² ( green/yellow)
Leads
16 mm ² (green/yellow)
Fuses, better: protective motor switches
acc. to EN 60742
N-conductor:
4 mm ² (green/yellow)
Use only with
permission of
the operator!
e.g. drives
Overvoltage category I
(1)
PE bars are to be installed preferably on the mounting plate.
In case of isolated PB bars, both ends must be connected to the mounting plate
by means of copper strips with a maximum length of 20 cm.
The cross-section of the copper strips has to be at least equal to that of the incoming cable.
Fig. 8-5:
Power routing 230 V
DANGER
Connect power supply units generating protective extra-low voltage
(PELV) (24 V) only to the supply voltages they are designed for. Comply
with the overvoltage categories (see
Do not apply the supply voltage to the protective extra-low voltage
(PELV)
Bosch Rexroth AG
30 el
cos (30 ) = 0.866
0
To the housing of the control cabinet
To the machine
6 mm² ( green/yellow)
All housing parts (functional ground)
PE neutral point
16 mm ² (green/yellow)
4 mm ² (green/yellow)
400V
Transformer
230V
(1)
PE
PE
N
U2
4 mm ² (green/yellow)
230 V power supply
operator terminals
service plug receptacle(s)
Power unit
VAP01.1H-W23
024-010-NN
Power unit
VAP01.1H-W23
024-010-NN
DC 24 V
Danger of lethal injury due to hazardous elec‐
tric voltage
"Power routing 230 V" on page
39/69
Interfaces
t
Overvoltage category III
Overvoltage category II
Terminals in
isolated
arrangement
DC 24 V
U
L
0 V
U
L
U
Q
U
0 V
Q
39)