EMC Immunity Type Tests per IEEE 1613
Note
The RUGGEDCOM RSG920P meets Class 2 requirements for an all-fiber
configuration and Class 1 requirements for copper ports. Class 1 allows for
temporary communication loss, while Class 2 requires error-free and interrupted
communications.
Electrostatic Discharge (ESD)
Burst (Electrical Fast Transient)
Environmental Type Tests
IEC 60068-2-1
IEC 60068-2-2
IEC 60068-2-30
IEC 60068-2-78
IEC 60068-14
IEC 60255-21-1
IEC 60255-21-2
RUGGEDCOM RSG920P
Installation Manual, 04/2021, C79000-G8976-1172-07
Description
Radiated Radio Frequency
Immunity (RFI)
Damped Oscillatory Wave
Dielectric Strength
Damped Oscillatory
Magnetic Field
Test
Cold Temperature
Dry Heat
Humidity (Damp
Heat, Cyclic)
Damp Heat
Steady State
Change of
Temperature
6.2 EMC and Environmental Type Tests
Enclosure
Contact
Enclosure
Contact
Enclosure Ports
35 V/m (80% Modulation)
Signal Ports
DC Power Ports
AC Power Ports
Earth
Ground Ports
Signal Ports
2.5 kV Common Mode at 1 MHz
DC Power Port
2.5 kV Common and
Differential Mode at 1 MHz
AC Power Port
2.5 kV Common and
Differential Mode at 1 MHz
Signal Ports
DC Power Port
AC Power Port
Enclosure Ports
100 A/m (Peak) at
100 kHz and 1 MHz
Description
Test Ad
Test Bd
Test Db
Test Cab
Test Nb
Vibration
Shock
Test Levels
±8 kV
±15 kV
±4 kV at 2.5 kHz
±4 kV
±4 kV
±4 kV
2 kV
2 kV
2 kV
Test Levels
Severity Levels
-40 °C (-40
°F), 16 Hours
85 °C (185
°F), 16 Hours
95% Relative
Humidity, 55 °C
(131 °F), 6 Cycles
93% Humidity,
10 Days
5 Cycles
2 g at 10-150 Hz
30 g at 11 ms
Certification
Severity
Levels
 
 
 
 
 
5
 
 
 
 
 
Class 1
Class 1
45