Vent Configuration: Horizontal Termination With Vertical Rise - Lopi ProBuilder 24 CleanFace GSR2 Installation Manual

Hide thumbs Also See for ProBuilder 24 CleanFace GSR2:
Table of Contents

Advertisement

Vent Configuration: Horizontal Termination with Vertical Rise

Vent configurations 7' (2.133m)or above (from the base of the fireplace) use 6-5/8" dia. vent.
Connect an 8" to 6-5/8" reducer directly to the fireplace (98900165).
NOTE: For this configuration, the included thimble assembly is not required and may be discarded.
Vent configurations under 15' (4.57m) (from the base of the fireplace) use 8" dia. Vent.
NOTE: For this configuration, the included thimble assembly may be used or use a firestop (not
included).
The termination must fall within the shaded area shown in the chart. Use the indicated restrictor
positions.
Up to four elbows (45° or 90°) may be used. Only one horizontal elbow may be used.
This is considered a horizontal
elbow (it does not matter
whether it turns right or left).
It may be a 90° or 45° elbow.
© Travis Industries
Installation
(for qualified installers only)
H2
H1
12/17/20 - 1528
Horizontal length is calculated by adding
both lengths of horizontal run
(Horizontal Length = H1 + H2).
This is considered a
vertical elbow
29
PB24 CF Install (AUST)