Vent Configurations

Minimum Vent Configuration

 Use 5x8" Diameter Coaxial Vent
 NOTE: Use the included thimble assembly whenever passing through a wall. (use
on front and back of wall penetration). See picture below.
 The termination must fall within the shaded area shown in the chart. Use the
indicated restrictor positions.
 One 45° elbow may be used on the horizontal run.
 HINT: Use minimum vent kit "H" (96200332) from Travis Industries (additional vent
may be required).
Min. 0.3M vertical and 90 Deg. Elbow
5 feet (1.524m)
3 feet (0.915m)
0 feet
Use the included wall thimble when
penetrating a wall. Part #96200101
© Travis Industries
Installation
(for qualified installers only)
Approx. 53-7/8"
(1369mm)
12/17/20 - 1528
Exhaust Restrictor # 1 (stock)
Diffuser Closed (stock)
Max. 3.4' (1.2M) Horizontal
27
PB24 CF Install (AUST)